Plan Review Notes
Plan Review Notes For Permit 12030117
Permit Number 12030117
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-03-09 13:23:011016 CLARE AVENUE - SUITE #4
 PERMIT #12030117
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THE USE OF FIRE RATED GYPSUM BOARD
 FOR ALL NEW PARTITIONS. ARE ALL OPENINGS AND
 PENETRATIONS INTENDED TO BE PROTECTED?
  
 INDICATE EXISTING WALLS THAT HAVE A FIRE RATING WITH
 PROTECTED OPENINGS AND PENETRATIONS.
  
 ALL FIRE RATED DOORS SHALL BE SELF CLOSING AND POSITIVE
 LATCHING.
  
 PROVIDE A PERMANENT SIGN ON THE CORRIDOR DOOR OF THE
 FIRE ROOM INDICATING "FACP" AND "SPR RISER".
  
 FIRE SPRINKLERS WILL NEED TO BE ADDED/RELOCATED TO
 ACCOUNT FOR THE NEW ROOMS AND NEW WALL LOCATIONS.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  