Plan Review Notes
Plan Review Notes For Permit 12030094
Permit Number 12030094
Review Stop E
Sequence Number 1
Notes
Date Text
2012-03-08 13:08:2312030094
 1449 8TH ST.
 INTERIOR RENOVATION
  
 PROVIDE AN ELECTRIC SERVICE RISER PLAN WITH WIRE SIZES,
 GROUNDING ETC. INDICATE THE LOCATION OF THE SERVICE.
 SHOW LOCATION OF MAIN BREAKER AND METER. NEC 215.15
 THE MAIN SERVICE DISCONNECT MUST BE LOCATED NEAREST THE
 POINT OF ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 FOR THE NEW WALL SPACES ADD RECEPTACLES SO THAT NO WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE AND ALL
 WALL SPACES MORE THAN 2 FEET IN WIDTH HAVE A RECEPTACLE
 I.E. NEW CLOSET WALL. NEC 210.52
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 ALL NEW RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC
 406.11
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  