Plan Review Notes For Permit 12030094 |
Permit Number |
12030094 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-03-19 13:52:21 | 2007 FBC W/2009 REVISIONS | | | | 1) THE PRODUCT APPROVAL FOR THE EXTERIOR GLAZED DOOR | | HAS DESIGN PRESSURES OF + 48 , -51 PSF AND THE PLANS | | SPECIFY THE REQUIRED PRESSURES FOR A 10 SQFT OPENING OF | | +56, -55 PSF. PLEASE SUBMIT PRODUCT APPROVALS FOR A | | DOOR WITH DESIGN PRESSURES GREATER THAN THE ONES | | SPECIFIED ON THE PLANS. FBC R301.2.1 | | | | 2) THE GLAZED EXTERIOR DOOR IS REQUIRED BY FBCR | | 301.2.1.2 AND EXISTING BUILDING 606.4 TO HAVE OPENING | | PROTECTION FROM WIND BORNE DEBRIS. THE PRODUCT APPROVAL | | THAT WAS SUBMITTED IS FOR A NON-IMPACT GLAZED DOOR. | | SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR STORM PANELS | | AND INSTALLATION SCHEDULES FOR THE NEW GLAZED DOORS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|