2012-03-19 13:52:212007 FBC W/2009 REVISIONS
  
 1) THE PRODUCT APPROVAL FOR THE EXTERIOR GLAZED DOOR
 HAS DESIGN PRESSURES OF + 48 , -51 PSF AND THE PLANS
 SPECIFY THE REQUIRED PRESSURES FOR A 10 SQFT OPENING OF
 +56, -55 PSF. PLEASE SUBMIT PRODUCT APPROVALS FOR A
 DOOR WITH DESIGN PRESSURES GREATER THAN THE ONES
 SPECIFIED ON THE PLANS. FBC R301.2.1
  
 2) THE GLAZED EXTERIOR DOOR IS REQUIRED BY FBCR
 301.2.1.2 AND EXISTING BUILDING 606.4 TO HAVE OPENING
 PROTECTION FROM WIND BORNE DEBRIS. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED IS FOR A NON-IMPACT GLAZED DOOR.
 SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR STORM PANELS
 AND INSTALLATION SCHEDULES FOR THE NEW GLAZED DOORS.
  