Plan Review Notes
Plan Review Notes For Permit 12030044
Permit Number 12030044
Review Stop B
Sequence Number 2
Notes
Date Text
2012-07-25 16:40:46BUILDING PLAN REVIEW
 PERMIT: 12030044
 ADD: 4847 FRED GLADSTONE
 CONT: THE WHITING TURNER CO.
 TEL: (954)776-0800
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 7/25/2012
 ACTION: DENIED
  
 1-4E) COMPLIED.
  
  
  
 4F) FIRE/ SMOKE PARTITIONS INSPECT 2007/09 FBC-B
 420.3.10.21 WHERE IT IS NOT POSSIBLE TO INSPECT
 FIRE/SMOKE PARTITIONS BECAUSE OF THE FIRE-TESTED
 MEMBRANE, FIRE-RATED ACCESS PANELS SHALL BE INSTALLED
 ADJACENT TO EACH SIDE OF THE SMOKE PARTITIONS AT
 INTERVALS NOT EXCEEDING 30 FEET (9.00 M) AND IN SUCH
 LOCATIONS AS NECESSARY TO VIEW ALL SURFACES OF THE
 PARTITION. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING. SUCH IDENTIFICATION SHALL BE ABOVE ANY
 DECORATIVE CEILING AND IN CONCEALED SPACES. SUGGESTED
 WORDING FOR A FIRE/SMOKE PARTITION IS AS FOLLOWS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
  
 4G) THIS WILL BE A COMMON STATEMENT FOR ALL SLEEPING
 UNITS FOR ALL COMPARTMENTS ON ALL FLOORS, THIS SHEET
 NOR IF SHEETS INDICATE HOW MANY OCCUPANTS ARE IN A ROOM
 NOR IS THERE A FURNITURE LAYOUT THAT WILL ALLOW FOR
 CODE COMPLIANCE FOR SECTION 403.2.2 & 403.2.3 FOR UNIT
 TYPES A-E.
  
 4H-4M) COMPLIED.
  
 4N)ALTERNATE MATERIALS & METHODS, CURRENTLY UNDER
 CONSIDERATION BY THE BUILDING OFFICIAL.
 COMMENT COMMEND TO ALL FLOORS. 2007/09 FBC-B 420.3.2.6
 DOORS TO RESIDENT TOILET ROOMS SHALL BE SIDE HINGED.
 PLEASE ALSO NOTE THE HARDWARE SCHEDULE DOES NOT
 INDICATE TYPE OF HARDWARE THAT WOULD MEET THE
 ACCESSIBILITY CODE 11-4.13.9.
  
 4O) COMMENT COMMON TO ALL FLOORS. 2007/09 FBC-B
 420.3.2.7 EACH RESIDENT SHALL HAVE A WARDROBE, LOCKER
 OR CLOSET FOR EACH RESIDENT.
  
  
 4P-4V) COMPLIED.
  
  
 5-7) COMPLIED.
  
 NEW COMMENT: SHEETS A-105, A106 & A-107 LOADED WRONG.
  
 8) SHEET A106 ROOF PLAN: EIGHT ROOF DRAINS ARE MISSING
 A EMERGENCY ROOF DRAIN. THE OVERFLOW SCUPPERS THAT ARE
 SHOWN (6) ARE LOCATED SOMEWHERE BETWEEN 2?- 4? ABOVE
 THE EDGE OF THE INSULATED ROOF. 1503.4.3 OVERFLOW
 SCUPPERS ARE DESIGNED TO BE USED WITH SCUPPERS WHERE
 THE ROOF SLOPES TO THE SCUPPERS, AND IF THE SCUPPERS
 ARE BLOCKED THEN THE OVERFLOW SCUPPERS WILL ONLY POND
 2-4 INCHES. WITH THE ROOF HAVING ??/ 12? OR 1? PER
 4?-0? AND THE ROOF DRAIN TO THE OVER FLOW SCUPPER IS 32
 FEET AWAY THE PONDING WOULD BE 8-10 INCHES DEEP.
  
 9-10) COMPLIED.
  
 11) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, SOLID & GLAZED, ROLL UP OR
 COILING OVERHEAD DOORS AND OR INCLUDING ROOF HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E SKYLIGHTS
 (F) PRE-ENGINEERED A/C STANDS
  
 NEW COMMENT:
 ROOF TILE 05-0901.06 EXPIRED 12/16/07
 NOA 08-0528 AUTO-SLIDDERS/ NON- IMPACT, NO TECHNICAL
 SHEETS PROVIDED.
 NOA 08-0715.14 STOREFRONT / NON-IMPACT, NO TECHNICAL
 SHEETS PROVIDED.
 NOA 09-0121.10 FIXED WINDOW LMI NO TECHNICAL SHEETS
 PROVIED.
 NOA 09-0923.09 AMWELD OUTSWING DOOR NO TECHNICAL SHEETS
 PROVIDED.
 NOA 11-0119.24 LOUVER, NO TECHNICAL SHEETS PROVIDED.
 NOA 11-0822.10 NO TECHNICAL SHEETS PROVIDED.
 NOA 12-0206.11 NO TECHNICAL SHEETS PROVIDED.
 NOA 11-0722.10 BILCO ROOF HATCH NO TECHNICAL SHEETS
 PROVIDED.
  
 12) FBC-B 1609.1.2 PROTECTION OF OPENINGS. LARGE IMPACT
 RESISTANT GLAZING TO A HEIGHT OF 30'-0" OR :
 420.4.2.5.2 PERMANENTLY ATTACHED PROTECTIVE SYSTEMS
 SUCH AS SHUTTERS AND BAFFLING SHALL BE DESIGNED TO MEET
 THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE DEBRIS
 IMPACT REQUIREMENTS AS SPECIFIED BY SECTIONS 1626.2
 THROUGH 1626.4.
  
 420.4.2.5.3 REMOVABLE PROTECTIVE SYSTEMS DESIGNED TO
 INTRICATELY FIT WITH THE WALL/WINDOW SYSTEM OF THE
 FACILITY AND STORED ON SITE AT THE FACILITY AND THAT
 MEET THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE
 DEBRIS IMPACT REQUIREMENTS SPECIFIED BY SECTIONS 1626.2
 THROUGH 1626.4 MAY BE USED TO PROTECT THE EXTERIOR
 UNITS.
  
  
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  