2012-07-25 16:40:46 | BUILDING PLAN REVIEW |
| PERMIT: 12030044 |
| ADD: 4847 FRED GLADSTONE |
| CONT: THE WHITING TURNER CO. |
| TEL: (954)776-0800 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2ND REVIEW |
| 7/25/2012 |
| ACTION: DENIED |
| |
| 1-4E) COMPLIED. |
| |
| |
| |
| 4F) FIRE/ SMOKE PARTITIONS INSPECT 2007/09 FBC-B |
| 420.3.10.21 WHERE IT IS NOT POSSIBLE TO INSPECT |
| FIRE/SMOKE PARTITIONS BECAUSE OF THE FIRE-TESTED |
| MEMBRANE, FIRE-RATED ACCESS PANELS SHALL BE INSTALLED |
| ADJACENT TO EACH SIDE OF THE SMOKE PARTITIONS AT |
| INTERVALS NOT EXCEEDING 30 FEET (9.00 M) AND IN SUCH |
| LOCATIONS AS NECESSARY TO VIEW ALL SURFACES OF THE |
| PARTITION. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, |
| SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| STENCILING. SUCH IDENTIFICATION SHALL BE ABOVE ANY |
| DECORATIVE CEILING AND IN CONCEALED SPACES. SUGGESTED |
| WORDING FOR A FIRE/SMOKE PARTITION IS AS FOLLOWS: "FIRE |
| AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| |
| |
| 4G) THIS WILL BE A COMMON STATEMENT FOR ALL SLEEPING |
| UNITS FOR ALL COMPARTMENTS ON ALL FLOORS, THIS SHEET |
| NOR IF SHEETS INDICATE HOW MANY OCCUPANTS ARE IN A ROOM |
| NOR IS THERE A FURNITURE LAYOUT THAT WILL ALLOW FOR |
| CODE COMPLIANCE FOR SECTION 403.2.2 & 403.2.3 FOR UNIT |
| TYPES A-E. |
| |
| 4H-4M) COMPLIED. |
| |
| 4N)ALTERNATE MATERIALS & METHODS, CURRENTLY UNDER |
| CONSIDERATION BY THE BUILDING OFFICIAL. |
| COMMENT COMMEND TO ALL FLOORS. 2007/09 FBC-B 420.3.2.6 |
| DOORS TO RESIDENT TOILET ROOMS SHALL BE SIDE HINGED. |
| PLEASE ALSO NOTE THE HARDWARE SCHEDULE DOES NOT |
| INDICATE TYPE OF HARDWARE THAT WOULD MEET THE |
| ACCESSIBILITY CODE 11-4.13.9. |
| |
| 4O) COMMENT COMMON TO ALL FLOORS. 2007/09 FBC-B |
| 420.3.2.7 EACH RESIDENT SHALL HAVE A WARDROBE, LOCKER |
| OR CLOSET FOR EACH RESIDENT. |
| |
| |
| 4P-4V) COMPLIED. |
| |
| |
| 5-7) COMPLIED. |
| |
| NEW COMMENT: SHEETS A-105, A106 & A-107 LOADED WRONG. |
| |
| 8) SHEET A106 ROOF PLAN: EIGHT ROOF DRAINS ARE MISSING |
| A EMERGENCY ROOF DRAIN. THE OVERFLOW SCUPPERS THAT ARE |
| SHOWN (6) ARE LOCATED SOMEWHERE BETWEEN 2?- 4? ABOVE |
| THE EDGE OF THE INSULATED ROOF. 1503.4.3 OVERFLOW |
| SCUPPERS ARE DESIGNED TO BE USED WITH SCUPPERS WHERE |
| THE ROOF SLOPES TO THE SCUPPERS, AND IF THE SCUPPERS |
| ARE BLOCKED THEN THE OVERFLOW SCUPPERS WILL ONLY POND |
| 2-4 INCHES. WITH THE ROOF HAVING ??/ 12? OR 1? PER |
| 4?-0? AND THE ROOF DRAIN TO THE OVER FLOW SCUPPER IS 32 |
| FEET AWAY THE PONDING WOULD BE 8-10 INCHES DEEP. |
| |
| 9-10) COMPLIED. |
| |
| 11) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS, SOLID & GLAZED, ROLL UP OR |
| COILING OVERHEAD DOORS AND OR INCLUDING ROOF HATCHES. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E SKYLIGHTS |
| (F) PRE-ENGINEERED A/C STANDS |
| |
| NEW COMMENT: |
| ROOF TILE 05-0901.06 EXPIRED 12/16/07 |
| NOA 08-0528 AUTO-SLIDDERS/ NON- IMPACT, NO TECHNICAL |
| SHEETS PROVIDED. |
| NOA 08-0715.14 STOREFRONT / NON-IMPACT, NO TECHNICAL |
| SHEETS PROVIDED. |
| NOA 09-0121.10 FIXED WINDOW LMI NO TECHNICAL SHEETS |
| PROVIED. |
| NOA 09-0923.09 AMWELD OUTSWING DOOR NO TECHNICAL SHEETS |
| PROVIDED. |
| NOA 11-0119.24 LOUVER, NO TECHNICAL SHEETS PROVIDED. |
| NOA 11-0822.10 NO TECHNICAL SHEETS PROVIDED. |
| NOA 12-0206.11 NO TECHNICAL SHEETS PROVIDED. |
| NOA 11-0722.10 BILCO ROOF HATCH NO TECHNICAL SHEETS |
| PROVIDED. |
| |
| 12) FBC-B 1609.1.2 PROTECTION OF OPENINGS. LARGE IMPACT |
| RESISTANT GLAZING TO A HEIGHT OF 30'-0" OR : |
| 420.4.2.5.2 PERMANENTLY ATTACHED PROTECTIVE SYSTEMS |
| SUCH AS SHUTTERS AND BAFFLING SHALL BE DESIGNED TO MEET |
| THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE DEBRIS |
| IMPACT REQUIREMENTS AS SPECIFIED BY SECTIONS 1626.2 |
| THROUGH 1626.4. |
| |
| 420.4.2.5.3 REMOVABLE PROTECTIVE SYSTEMS DESIGNED TO |
| INTRICATELY FIT WITH THE WALL/WINDOW SYSTEM OF THE |
| FACILITY AND STORED ON SITE AT THE FACILITY AND THAT |
| MEET THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE |
| DEBRIS IMPACT REQUIREMENTS SPECIFIED BY SECTIONS 1626.2 |
| THROUGH 1626.4 MAY BE USED TO PROTECT THE EXTERIOR |
| UNITS. |
| |
| |
| PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR |
| WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13 |
| RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES |
| WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE |
| SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT |
| MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE |
| THAT COMPLETE INSTALLATION OR SECURING IS DONE |
| SUFFICIENTLY IN ADVANCE OF THE HURRICANE? |
| |
| IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING, |
| CHAPTER 1, |
| ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY |
| OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE |
| BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR |
| ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION |
| OF EXISTING BUILDINGS. |
| |
| IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR |
| MULTI-STORY BUILDINGS, OR MULTIPLE |
| ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST |
| BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS |
| FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY |
| SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION |
| OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH |
| COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN |
| TWELVE (12) HOURS OR LESS OF THE |
| OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES |
| OF A HURRICANE WATCH. |
| |
| PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE |
| MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN |
| QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, |
| DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| |
| IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM |
| SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/ |
| 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT |
| PROTECTION. |
| |
| 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |