Plan Review Notes
Plan Review Notes For Permit 12030044
Permit Number 12030044
Review Stop P
Sequence Number 1
Notes
Date Text
2012-04-09 11:12:32FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEETS P101, P103, P104, P208 PER TABLE 1106.3
 HORIZONTAL STORM PIPING - 5" RAINFALL RATE THE
 HORIZONTAL PIPING ON THE FIRST AND OFFSETS TO ROOF
 WOULD BE REQUIRED TO HAVE 1/4" PER FOOT FALL.
  
 2. SHEETS 202 & 203 OXYGEN LINE APPEARS TO BE
 INTERCONNECTED WITH THE COLD WATER NEAR COLUMN LINE
 J-5.
  
 3. SHEET P301- THE S-4 SINKS ARE NOT SHOWN AS BEING
 VENTED. TRAPS SHOULD BE SHOWN FOR FS-1 FIXTURES. A VTR
 IS MISSING FOR SOILED UTILLITY
  
 4. SHEET P501 THE BOTTOM FED WATER HEATERS WILL REQUIRE
 ANSI Z21.22 VACUUM RELIEF. SECTION 504.2
  
 5. FUEL GAS IS NOT PART OF THIS REVIEW. SEPARATE PLAN,
 REVIEW, APPLICATION, AND PERMIT REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  