Plan Review Notes For Permit 12030044 |
Permit Number |
12030044 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-04-09 11:12:32 | FBC 2007 PLUMBING REVIEW #1 | | DENIED: | | | | 1. SHEETS P101, P103, P104, P208 PER TABLE 1106.3 | | HORIZONTAL STORM PIPING - 5" RAINFALL RATE THE | | HORIZONTAL PIPING ON THE FIRST AND OFFSETS TO ROOF | | WOULD BE REQUIRED TO HAVE 1/4" PER FOOT FALL. | | | | 2. SHEETS 202 & 203 OXYGEN LINE APPEARS TO BE | | INTERCONNECTED WITH THE COLD WATER NEAR COLUMN LINE | | J-5. | | | | 3. SHEET P301- THE S-4 SINKS ARE NOT SHOWN AS BEING | | VENTED. TRAPS SHOULD BE SHOWN FOR FS-1 FIXTURES. A VTR | | IS MISSING FOR SOILED UTILLITY | | | | 4. SHEET P501 THE BOTTOM FED WATER HEATERS WILL REQUIRE | | ANSI Z21.22 VACUUM RELIEF. SECTION 504.2 | | | | 5. FUEL GAS IS NOT PART OF THIS REVIEW. SEPARATE PLAN, | | REVIEW, APPLICATION, AND PERMIT REQUIRED. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|