2012-06-25 08:21:42 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2010 | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. GATE HOUSE AND GENERATOR ARE TO BE COVERED UNDER | | SEPARATE PERMITS. | | | | 2. PAGE M201 DRYER EXHAUST DUCTS PENETRATING 1-HR RATED | | WALL AT MULTIPLE LOCATIONS. SHOW HOW THESE PENETRATIONS | | ARE TO BE PROTECTED PER FBC-M 607.1.1. | | | | 3. PAGE M202 DRYER EXHAUST DUCTS PENETRATING 1-HR RATED | | WALL AT MULTIPLE LOCATIONS. SHOW HOW THESE PENETRATIONS | | ARE TO BE PROTECTED PER FBC-M 607.1.1. | | | | 4. PRODUCT APPROVAL IS REQQUIRED FOR ALL PRE-ENGINEERED | | AC STANDS PER FBC-M 301.12 AND FAC RULE 9N.1. PRODUCT | | APPROVALS SHALL BE APPROVED IN WRITING BY THE DESIGN | | PROFESSIONAL (SHOP DRAWING REVIEW STAMP WILL SUFFICE). | | | | 5. PROVIDE DRYER MANUFACTURER'S INSTALLATION | | INSTRUCTIONS SHOWING THE MAX ALLOWABLE LENGTH OF DRYER | | EXHAUST DUCT PER FBC-M 504.1 OR FBC-M 504.7 AS | | APPLICABLE. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|