Plan Review Notes
Plan Review Notes For Permit 12030044
Permit Number 12030044
Review Stop E
Sequence Number 1
Notes
Date Text
2012-03-30 15:53:4212030044
 4847 FRED GLADSTONE DR.
 TYPE IIIA 3 STORY BUILDING
 INSTITUTIONAL GROUP I-2
  
 E000
 UPDATE THE PLAN WITH A LEGEND AND GENERAL NOTES.
 INCLUDE A CONDUIT SCHEDULE FOR BRANCH CIRCUITS AND
 FEEDERS
 E001
 PLEASE CLARIFY THE FEEDER SIZE PROPOSED FOR ATS ?LS.
 BOTH 250 KCMIL AND 500KCMIL HAVE BEEN PROPOSED.
 CLARIFY HOW THE GENERATOR QUICK CONNECT WILL FUNCTION
 SAFELY.
 E102
 CLARIFY THE USE OF ALUMINUM EQUIPMENT GROUNDING
 CONDUCTORS. THE GENERAL RULE SUGGESTS THAT GROUNDING
 CONDUCTORS WHICH FACILITATE THE BONDING OF PANEL BOARDS
 SHOULD BE COPPER. NEC 517.11
 E002
 PROVIDE SERVICE RISER SPECIFICATION FOR GUARD SHACK
 TRANSFORMER AND PANEL EQLGS. PROVIDE GROUND ROD AND
 NEUTRAL TO BOND AT GUARD SHACK.
 CLARIFY/COORDINATE AND UPDATE THE RISER PLAN AND PANEL
 SCHEDULES FOR THE FEEDER AND LOADS FOR THE KITCHEN
 PANEL EQLB1.
 NEC 215.5
 E003
 VERIFY THE 112 ? KVA TRANSFORMERS OR LARGER ARE LOCATED
 WITHIN FIRE-RESISTANT ROOMS WITH A ONE HOUR FIRE RATING
 OR COMPLY WITH THE NEC EXCEPTIONS. NEC 450.21 (B)
 E203
 A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR
 EQUIPMENT ROOMS. NEC 620.23
 E501A
 FIRE PUMP ROOM REQUIRES A 2 HOUR FIRE RATING. FBC
 420.3.19
 VERIFY ALL CIRCUIT CONDUCTORS AND CONTROL WIRING FOR
 THE FIRE PUMP AND GENERATOR ARE INDEPENDENT AND HAVE A
 MINIMUM OF 2 HOUR AND 1 HOUR FIRE PROTECTION
 RESPECTIVELY. NEC 695.6, 605.14
 E600
 PROVIDE A DETAIL WHICH ILLUSTRATES THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED AS REQUIRED FOR THE ELECTRICAL EQUIPMENT AND
 PANEL BOARDS. NEC 110.26, 240.24, 408.17
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING
 THE SIZE AND TYPE OF HAZARDS. NEC 110.22, 110.16
 E602
 A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR
 EQUIPMENT ROOMS. NEC 620.23
 E301A
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 CLARIFY OR SUMMARIZE ON THE PLAN HOW THE LIGHTING WILL
 BE CONTROLLED USING MOTION SENSORS OR SIMILAR
 TECHNIQUES. SPACE CONTROL FBC 13-415 ABC.1.2.
 ADDITIONAL CONTROLS 13-415.ABC.1.3
 P101
 BUILDING DRAINS APPEAR TO CROSS THROUGH AND OVER THE
 ELECTRICAL EQUIPMENT WITHIN THE SPACE DEDICATED TO THE
 EQUIPMENT. NEC 110.26 (F)
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, LIGHTNING PROTECTION, NURSE CALL, VOICE
 AND DATA.
 A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING
 FOR POLES, BASES AND FIXTURES IS REQUIRED.
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER