| 4847 FRED GLADSTONE DR. |
| TYPE IIIA 3 STORY BUILDING |
| INSTITUTIONAL GROUP I-2 |
| |
| E000 |
| UPDATE THE PLAN WITH A LEGEND AND GENERAL NOTES. |
| INCLUDE A CONDUIT SCHEDULE FOR BRANCH CIRCUITS AND |
| FEEDERS |
| E001 |
| PLEASE CLARIFY THE FEEDER SIZE PROPOSED FOR ATS ?LS. |
| BOTH 250 KCMIL AND 500KCMIL HAVE BEEN PROPOSED. |
| CLARIFY HOW THE GENERATOR QUICK CONNECT WILL FUNCTION |
| SAFELY. |
| E102 |
| CLARIFY THE USE OF ALUMINUM EQUIPMENT GROUNDING |
| CONDUCTORS. THE GENERAL RULE SUGGESTS THAT GROUNDING |
| CONDUCTORS WHICH FACILITATE THE BONDING OF PANEL BOARDS |
| SHOULD BE COPPER. NEC 517.11 |
| E002 |
| PROVIDE SERVICE RISER SPECIFICATION FOR GUARD SHACK |
| TRANSFORMER AND PANEL EQLGS. PROVIDE GROUND ROD AND |
| NEUTRAL TO BOND AT GUARD SHACK. |
| CLARIFY/COORDINATE AND UPDATE THE RISER PLAN AND PANEL |
| SCHEDULES FOR THE FEEDER AND LOADS FOR THE KITCHEN |
| PANEL EQLB1. |
| NEC 215.5 |
| E003 |
| VERIFY THE 112 ? KVA TRANSFORMERS OR LARGER ARE LOCATED |
| WITHIN FIRE-RESISTANT ROOMS WITH A ONE HOUR FIRE RATING |
| OR COMPLY WITH THE NEC EXCEPTIONS. NEC 450.21 (B) |
| E203 |
| A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR |
| EQUIPMENT ROOMS. NEC 620.23 |
| E501A |
| FIRE PUMP ROOM REQUIRES A 2 HOUR FIRE RATING. FBC |
| 420.3.19 |
| VERIFY ALL CIRCUIT CONDUCTORS AND CONTROL WIRING FOR |
| THE FIRE PUMP AND GENERATOR ARE INDEPENDENT AND HAVE A |
| MINIMUM OF 2 HOUR AND 1 HOUR FIRE PROTECTION |
| RESPECTIVELY. NEC 695.6, 605.14 |
| E600 |
| PROVIDE A DETAIL WHICH ILLUSTRATES THE REQUIRED WORKING |
| CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN |
| PROVIDED AS REQUIRED FOR THE ELECTRICAL EQUIPMENT AND |
| PANEL BOARDS. NEC 110.26, 240.24, 408.17 |
| PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL |
| EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING |
| THE SIZE AND TYPE OF HAZARDS. NEC 110.22, 110.16 |
| E602 |
| A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR |
| EQUIPMENT ROOMS. NEC 620.23 |
| E301A |
| PROVIDE A LIGHTING DENSITY CALCULATION SHOWING |
| COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| REQUIREMENTS. FBC 13-415 ABC.5 |
| CLARIFY OR SUMMARIZE ON THE PLAN HOW THE LIGHTING WILL |
| BE CONTROLLED USING MOTION SENSORS OR SIMILAR |
| TECHNIQUES. SPACE CONTROL FBC 13-415 ABC.1.2. |
| ADDITIONAL CONTROLS 13-415.ABC.1.3 |
| P101 |
| BUILDING DRAINS APPEAR TO CROSS THROUGH AND OVER THE |
| ELECTRICAL EQUIPMENT WITHIN THE SPACE DEDICATED TO THE |
| EQUIPMENT. NEC 110.26 (F) |
| |
| NOTE: |
| SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE |
| ALARM SYSTEM, LIGHTNING PROTECTION, NURSE CALL, VOICE |
| AND DATA. |
| A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING |
| FOR POLES, BASES AND FIXTURES IS REQUIRED. |
| |