Plan Review Notes
Plan Review Notes For Permit 12030044
Permit Number 12030044
Review Stop B
Sequence Number 1
Notes
Date Text
2012-03-21 16:34:22 
 BUILDING PLAN REVIEW
 PERMIT: 12030044
 ADD: 4847 FRED GLADSTONE
 CONT: THE WHITING TURNER CO.
 TEL: (954)776-0800
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLEASE PROVIDE (3) SURVEY INDICATING WHAT FLOOD
 ZONE THIS NEW BUILDING WILL BE LOCATED. WPB ADMIN.
 106.3.5.1.
  
 1B) THERE ARE SEPARATE BUILDINGS AND FEATURES THAT ARE
 PART OF THIS PERMIT SET OF PLANS. SEPARATE ADDRESSES,
 PERMITS (PERMIT APPLICATIONS) AND ASSOCIATED FEES WILL
 BE REQUIRED FOR RECORD KEEPING PURPOSES (INSPECTIONS).
  
 2) PLEASE PROVIDE (3) ORIGINAL SOILS REPORTS 2007/09
 FBC-B1802.6.
  
 3) THIS BUILDING QUALIFIES FOR A SPECIAL RESIDENT
 INSPECTOR 109.3.7 WPB ADMIN.:
 A) TYPE II CONSTRUCTION
 B) FOR BUILDINGS WITH AN AREA GREATER THAN 20,000
 SQUARE FEET
 C) FOR BUILDINGS GREATER THAN 2 STORIES IN HEIGHT
 FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME'
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 4 SHEET A101, LIFE SAFETY SHEET G-101 AND A002
 PARTITION TYPES DO NOT MATCH UP:
  
 4A) STAIR # 3 OR ROOM # S103 WALL TAG TYPE F01 NO FIRE
 RATING VERSES G-101. FBC-B 1020.1.
  
 4B) STAIR # 3 WALL TAG MISSING, RATING FBC-B 1020.1.
  
 4C) STAIR # 3 SEE DETAIL # 1/ A451, WRONG PLAN UP
 LOADED, A551.
  
 4D) WALL TAG TYPE F01 IS INDICATED DRYWALL ON ONE SIDE,
 SEE
 FL. BOAF INFORMAL INTERPRETATIONS 6341 REQUIRING
 DRYWALL ON BOTH SIDES OF THE WALL.
  
 4E) COMMON STATEMENT FOR ALL FLOORS!!! SHEET A101
 VERSES G-101, LIFE SAFETY SHEETS INDICATE THE CORRIDOR
 WALLS TO BE SMOKE PARTITIONS AS REQUIRED BY SECTION
 2007/09 FBC-B 407.3 SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION 710 SMOKE PARTITIONS.
 PLEASE SEE BOAF INFORMAL INTERPRETATION # 6341.
 PLEASE PROVIDE ON SHEET A002 A HEADING TYPE FOR SMOKE
 PARTITIONS AND SMOKE BARRIER WALLS AS IS PROVIDED FOR
 FIRE RATED WALLS, ON THIS IDENTIFY WALL RATINGS.
 COMMON STATEMENT FOR ALL FLOORS!!! SHEET A101 VERSES
 G-101, LIFE SAFETY SHEETS INDICATE THE CORRIDOR WALLS
 TO BE SMOKE PARTITIONS AS REQUIRED BY SECTION 2007/09
 FBC-B 407.3 SMOKE PARTITIONS IN ACCORDANCE WITH SECTION
 710 SMOKE PARTITIONS. PLEASE PROVIDE ON SHEET A002 A
 HEADING TYPE FOR SMOKE PARTITIONS AND SMOKE BARRIER
 WALLS AS IS PROVIDED FOR FIRE RATED WALLS, ON THIS
 IDENTIFY WALL RATINGS.
  
  
 4F) FIRE/ SMOKE PARTITIONS INSPECT 2007/09 FBC-B
 420.3.10.21 WHERE IT IS NOT POSSIBLE TO INSPECT
 FIRE/SMOKE PARTITIONS BECAUSE OF THE FIRE-TESTED
 MEMBRANE, FIRE-RATED ACCESS PANELS SHALL BE INSTALLED
 ADJACENT TO EACH SIDE OF THE SMOKE PARTITIONS AT
 INTERVALS NOT EXCEEDING 30 FEET (9.00 M) AND IN SUCH
 LOCATIONS AS NECESSARY TO VIEW ALL SURFACES OF THE
 PARTITION. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING. SUCH IDENTIFICATION SHALL BE ABOVE ANY
 DECORATIVE CEILING AND IN CONCEALED SPACES. SUGGESTED
 WORDING FOR A FIRE/SMOKE PARTITION IS AS FOLLOWS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
  
 4G) THIS WILL BE A COMMON STATEMENT FOR ALL SLEEPING
 UNITS FOR ALL COMPARTMENTS ON ALL FLOORS, THIS SHEET
 NOR IF SHEETS INDICATE HOW MANY OCCUPANTS ARE IN A ROOM
 NOR IS THERE A FURNITURE LAYOUT THAT WILL ALLOW FOR
 CODE COMPLIANCE FOR SECTION 403.2.2 & 403.2.3 FOR UNIT
 TYPES A-E.
  
 4H) SMOKE COMPARTMENT/ SMOKE BARRIER FBC-B 407.4 WALL
 MISSING 1 HOUR FIRE RATING ON THIS SHEET AND A002, WALL
 TYPE A01 MISSING 1 HOUR FIRE RATING. SEE G-101.
  
 4I) COMMON TO ALL FLOORS. ELEVATOR SHAFT WALLS SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH FBC-B 706.5.
  
 4J) COMMON TO ALL FLOORS VERTICAL EXIT STAIRWELL.
 MISSING WALL IDENTIFICATION TAG.
 G-101 INDICATES A TWO HOUR FIRE RATING. FBC-B 1020.1.
  
 4K) STAIRWELL S101 EXIT DOES NOT DISCHARGE AT THE
 EXTERIOR OF THE BUILDING. IT ALSO DOES NOT MEET THE
 REQUIREMENTS OF A VESTIBULE FBC 1024.1. WALL RATINGS?
  
 4L) ROOM 166, DOOR # 166 PLEASE NOTE THAT ON SHEET THE
 DOOR SCHEDULE THE HARDWARE IS NOT SPECIFIED, FBC-B
 420.3.3.8 LOCKABLE DOOR IS REQUIRED.
  
  
  
  
 4M) ROOM 166 WALL TAG M03 DETAIL IS MISSING ON SHEET
 A002. G-101 INDICATES THIS WALL IS PART OF THE SMOKE
 PARTITION REQUIREMENTS FOR CORRIDOR. FBC 407.3/ 710.
  
 4N COMMENT COMMEND TO ALL FLOORS. 2007/09 FBC-B
 420.3.2.6 DOORS TO RESIDENT TOILET ROOMS SHALL BE SIDE
 HINGED. PLEASE ALSO NOTE THE HARDWARE SCHEDULE DOES NOT
 INDICATE TYPE OF HARDWARE THAT WOULD MEET THE
 ACCESSIBILITY CODE 11-4.13.9.
  
 4O) COMMENT COMMON TO ALL FLOORS. 2007/09 FBC-B
 420.3.2.7 EACH RESIDENT SHALL HAVE A WARDROBE, LOCKER
 OR CLOSET FOR EACH RESIDENT.
  
  
 4P) THIS COMMENT IS FOR ALL DINING AREAS FOR ALL
 FLOORS. PLEASE PROVIDE THE SQUARE FOOT AREA OF EACH
 DINING AREA AND THE AMOUNT OF RESIDENTS TO BE SERVED.
 2007/09 FBC ?B 420.3.4.1.
  
 4Q) PLANS DO NOT INDICATE COMPLIANCE WITH 2007/09 FBC-B
 420.3.4.4 A BARBER/BEAUTY ROOM SHALL BE PROVIDED WITH
 FACILITIES AND EQUIPMENT FOR RESIDENT HAIR CARE AND
 GROOMING. THE AREA OF THE ROOM SHALL BE A MINIMUM OF
 200 SQUARE FEET (18.58 M2) WITH THE LEAST DIMENSION OF
 12 FEET (3.66 M).
  
 4R) ROOM 130C SOILED UTILITY 2 OF THE WALL
 IDENTIFICATION TAGS ARE A01 PLEASE REVIEW G-101
 REFERENCING A 1-HOUR WALL RATING. FBC-B 420.3.3.6/ SEE
 REQUIREMENTS FROM NFPA 101 HAZARDOUS AREAS LIFE SAFETY
 CODE ADOPTED BY THE FLORIDA FIRE PREVENTION CODE.
  
 4S) COMMENT COMMON TO ALL FLOORS. PROVIDE COMPLIANCE
 WITH:
 2007/09 FBC-B 420.3.3.13 STORAGE ALCOVE SPACE FOR A
 MINIMUM OF ONE WHEELCHAIR AND ONE STRETCHER SHALL BE
 PROVIDED IN AN AREA LOCATED AWAY FROM NORMAL TRAFFIC.
  
 4T) STAIRWELL # 2 WALL IDENTIFICATION TAG INDICATES
 TYPE F, STEEL STUD WALL PLANS APPEAR TO BE A BLOCK WALL
 PLEASE PROVIDE WALL TYPE AND COMPLIANCE WITH FBC-B
 1020.1.
  
 4U) WINDOW HAZARDOUS LOCATION FBC-B 2406.3 (5) 5.
 GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS,
 WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS.
 GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING
 THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A
 STANDING SURFACE.
  
 4V) ROOM 172 A DOOR MAY REQUIRE 12" LATCH SIDE OF DOOR
 IN HALLWAY. NOTE DOOR SCHEDULE DOES NOT INDICATE
 HARDWARE.
 IF DOOR IS EQUIPPED WITH BOTH A DOOR CLOSER AND LATCH A
 CLEARANCE OF 112 INCHES IS REQUIRED.
  
 5) SHEET A-104 :
  
 5A) THE AREA OF THE GYMNASIUM IS APPROX 5340 SQ FT.
 SHEET G-0011 CODE SUMMARY DOES NOT PROVIDE THE SQUARE
 FOOTAGE PER FLOOR BUT IS INDICATING THE AREA INCREASE
 ALLOWED PER STORY IS 47,264. G101 DOES PROVIDE THE AREA
 OF THE THREE SMOKE COMPARTMENTS, TOTALING TO 36,565
 SQUARE FEET. THE AREA OF THE GYM IS OVER 10% OF THE
 FLOOR AREA (ACCESSORY OCCUPANCIES 508.3.1.) ACCESSORY
 OCCUPANCIES SHALL BE CLASSIFIED IN ACCORDANCE WITH
 SECTION 302.1. GYMNASIUMS ARE CLASSIFIED AS AN A-3
 OCCUPANCY FBC-B TABLE 508.3.3 WOULD REQUIRE 1 HOUR
 SEPARATION BETWEEN THE I-2 OCCUPANCY AND THE A-3
 GYMNASIUM WITH OPENING PROTECTION IN ACCORDANCE WITH
 FBC-B TABLE 715.4.
  
 5B) FL BC-B 11-6.1(3) LONG-TERM CARE FACILITIES AND
 NURSING HOMES. AT LEAST 50 PERCENT OF PATIENT BEDROOMS
 AND TOILETS, AND ALL PUBLIC USE AND COMMON USE AREAS
 ARE REQUIRED TO BE DESIGNED AND CONSTRUCTED TO BE
 ACCESSIBLE.
 IT APPEARS THAT THE BATHROOM 196A IS NOT ACCESSIBLE.
  
 5C) STORAGE ROOM 194A, LINEN STORAGE 190C, HOUSE
 KEEPING 194B & SOILED LINEN ROOM 190B DO NOT INDICATE
 ANY SMOKE AND OR FIRE RATINGS .
  
 5D) THERE IS AN UNIDENTIFIED AREA THAT APPEARS TO BE A
 RECEPTION COUNTER, ADDITIONAL INFORMATION IS REQUIRED,
 106.1.2/ 420.3.6.2.
  
 6) SHEET G102:
  
 6A) SMOKE COMPARTMENT WALL THAT SEPARATES COMPARTMENTS
 A/ B. WALL TYPE A01 & F01 BOTH ARE INDICATED AS NONE
 FIRE RATED. SMOKE COMPARTMENT WALLS REQUIRED BY 407.4
 SHALL BE IN ACCORDANCE WITH 709, 709.3 REQUIRES A 1
 HOUR SEPARATION CONTINUOUS FROM OUTSIDE OF WALL TO
 OUTSIDE OF WALL.
  
 6B) SATELLITE MAINTENANCE ROOM THE DOOR IS 45 MINUTE
 FIRE RATED BUT THE WALL DESIGNATION TAG A)! NO FIRE
 RATING. SEE G102 1 HR FIRE RATED.
  
 6C) CENTRAL STORAGE: G102 INDICATES THESE WALLS ALSO 1
 HOUR FIRE RATED WALLS.
  
 6D) ELEVATOR SHAFT WALL TAG DESIGNATION (F01) AS WELL
 AS STAIRWELL (STAIR # 1) WALLS 2 HRS IF FOUR STORIES OR
 MORE. FBC-B 1020.1.
  
 6E) SOILED UTILITY ROOM # 230C G102 INDICATES THE 1
 HOUR FIRE RATED WALLS FBC-B 420.3.3.6 NFPA 101
 CLASSIFIES AS HAZARDOUS LOCATION .
  
 6F) COMMON COMMENT TO ALL FLOORS. ROOM # 230A CART
 STORAGE, PLEASE PROVIDE ADDITIONAL INFORMATION, IT
 APPEARS THIS AREA MAY BE USED FOR LAUNDRY / LINEN CART
 STORAGE IF SO PLEASE PROVIDE DOCUMENTATION FOR A
 CLOSED-CART SYSTEM THAT WOULD BE IN COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, FBC-B 420.3.3.11.
  
 6G) WALL TYPE D01 ON G102 THIS WALL IS DESIGNATED AS A
 SMOKE PARTITION, PLEASE INDICATE COMPLIANCE WITH 710.
  
 7) SHEET G103:
  
 7A) MISSING INFORMATION ON WALL DESIGNATION TAG. SMOKE
 COMPARTMENT WALL/ SMOKE BARRIER FBC-B 709 1 HOUR RATING
 FROM OUTSIDE WALL TO OUTSIDE WALL.
  
 7B) SMOKE COMPARTMENT WALL THAT SEPARATES COMPARTMENTS
 A/ B. WALL TYPE A01 & F01 BOTH ARE INDICATED AS NONE
 FIRE RATED. SMOKE COMPARTMENT WALLS REQUIRED BY 407.4
 SHALL BE IN ACCORDANCE WITH 709, 709.3 REQUIRES A 1
 HOUR SEPARATION CONTINUOUS FROM OUTSIDE OF WALL TO
 OUTSIDE OF WALL.
  
 8) SHEET A106 ROOF PLAN: EIGHT ROOF DRAINS ARE MISSING
 A EMERGENCY ROOF DRAIN. THE OVERFLOW SCUPPERS THAT ARE
 SHOWN (6) ARE LOCATED SOMEWHERE BETWEEN 2?- 4? ABOVE
 THE EDGE OF THE INSULATED ROOF. 1503.4.3 OVERFLOW
 SCUPPERS ARE DESIGNED TO BE USED WITH SCUPPERS WHERE
 THE ROOF SLOPES TO THE SCUPPERS, AND IF THE SCUPPERS
 ARE BLOCKED THEN THE OVERFLOW SCUPPERS WILL ONLY POND
 2-4 INCHES. WITH THE ROOF HAVING ??/ 12? OR 1? PER
 4?-0? AND THE ROOF DRAIN TO THE OVER FLOW SCUPPER IS 32
 FEET AWAY THE PONDING WOULD BE 8-10 INCHES DEEP.
  
 9) SHEET S-6.6 WIND LOAD SCHEDULE INDICATES PRESSURES
 BUT NOT THE WIND DESIGN CRITERIA: 1609.6.2 WIND DESIGN
 PROCEDURES
 9.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
 9.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
 9.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4. NOTE THIS FACILITY HAS A
 BUILDING CATEGORY III, HEALTH CARE FACILITIES WITH A
 CAPACITY OF 50OR MORE RESIDENT PATIENTS BUT NOT HAVING
 SURGERY OR EMERGENCY TREATMENT FACILITIES.
 9.4 A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) EXPOSURE C
 9.5 POSITIVE & NEGATIVE PRESSURES FOR BOTH DOOR &
 WINDOW OPENINGS FOR SIZE OF OPENINGS, ROOF PRESSURES
 FOR FLAT ROOF AS WELL AS SLOPED ROOF 7 TO 27 DEGREES .
 9.6 MEAN ROOF HEIGHT- THE AVERAGE OF THE ROOF EAVE
 HEIGHT AND THE HEIGHT TO THE HIGHEST POINT ON THE ROOF
 SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR ROOF
 ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES (0.18 RAD).
  
 10) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 11) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, SOLID & GLAZED, ROLL UP OR
 COILING OVERHEAD DOORS AND OR INCLUDING ROOF HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E SKYLIGHTS
 (F) PRE-ENGINEERED A/C STANDS
  
 12) FBC-B 1609.1.2 PROTECTION OF OPENINGS. LARGE IMPACT
 RESISTANT GLAZING TO A HEIGHT OF 30'-0" OR :
 420.4.2.5.2 PERMANENTLY ATTACHED PROTECTIVE SYSTEMS
 SUCH AS SHUTTERS AND BAFFLING SHALL BE DESIGNED TO MEET
 THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE DEBRIS
 IMPACT REQUIREMENTS AS SPECIFIED BY SECTIONS 1626.2
 THROUGH 1626.4.
  
 420.4.2.5.3 REMOVABLE PROTECTIVE SYSTEMS DESIGNED TO
 INTRICATELY FIT WITH THE WALL/WINDOW SYSTEM OF THE
 FACILITY AND STORED ON SITE AT THE FACILITY AND THAT
 MEET THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE
 DEBRIS IMPACT REQUIREMENTS SPECIFIED BY SECTIONS 1626.2
 THROUGH 1626.4 MAY BE USED TO PROTECT THE EXTERIOR
 UNITS.
  
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved