Plan Review Notes For Permit 12030002 |
Permit Number |
12030002 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-03-01 11:31:38 | RE-ROOF REVISION BUILDING REVIEW COMMENTS. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- PLEASE PROVIDE FIELD WITHDRAWAL RESISTANCE TEST (TAS | | 105) AND RAS 117 CALCULATIONS AS REQUIRED BY | | LIGHTWEIGHT INSULATING CONCRETE SYSTEM LIMITATION #1 ON | | LAST PAGE OF NOA 11-0415.11 SUBMITTED. | | PROVIDE 2 SIGNED AND SEALED COPIES OF EACH. | | | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | TAKE INTO CONSIDERATION THAT PER 2009 REVISIONS, THIS | | BUILDING IS LOCATED ON EXPOSURE "C". | | | | 2- SELECTED APPROVED ASSEMBLY ON SHEET 8 OF NOA | | 11-0415.11 SUBMITTED IS GOOD FOR -52.5PSF. NEED TO | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2 | | COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST | | PAGE OF NOA TO MEET THE DESIGN PRESSRUES OF SEC. 1609 | | FBC. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|