Plan Review Notes For Permit 12020734 |
Permit Number |
12020734 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-02-29 15:10:57 | RESIDENTIAL (R3) FLAT ROOF AREA RE-ROOF BUILDING REVIEW | | COMMENTS. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PLEASE PROVIDE SIGNED AND SEALED RAS 117 | | CALCULATIONS (2 COPIES) AS REQUIRED TO MEET THE DESIGN | | PRESSURES OF SEC. R301.2.1.4.3. SIGNED AND SEALED | | CALCULATIONS ARE REQUIRED BY GENERAL LIMITATION #7 ON | | LAST PAGE OF NOA 08-0410.09 SUBMITTED. | | | | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON | | EXPOSURE "C". | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|