Plan Review Notes
Plan Review Notes For Permit 12020712
Permit Number 12020712
Review Stop B
Sequence Number 1
Notes
Date Text
2012-03-09 09:45:04****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FOR THE PROPOSED SHUTTERS, COMPLETE THE SAMPLE
 INSTALLATION SCHEDULE OR PROVIDE ALL INFORMATION TO
 SHOW CODE COMPLIANCE IN ANOTHER FORMAT, FBC*106, FBC
 R301, FBC1609. TWO SETS REQUIRED. THIS FORM IS
 AVAILABLE IN THE LOBBY OR ON THE INTERNET AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 2. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 2 ABOVE. FBC R301, FBC1609,
 FBC*106. SHOW LOCATIONS AND SIZES OF PROPOSED WINDOWS,
 DOORS.
  
 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
  
 4. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 SHUTTERS, DOORS.
  
  
  