 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE QUALIFIED SYSTEM DESIGNER NEEDS TO PROVIDE A
 SIGNATURE ON THE PLANS.
  
 PROVIDE THE CANDELA INTENSITY FOR THE VISUAL
 NOTIFICATION APPLIANCES.
  
 PROVIDE ROOM NAMES/NUMBERS ON THE PLANS SO THE LOCATION
 OF THE FIRE ALARM DEVICES CAN BE IDENTIFIED.
  
 PROVIDE BATTERY CALCULATIONS AS DEVICES HAVE BEEN ADDED
 TO THE EXISTING NOTIFICATION APPLIANCE CIRCUIT.
  
 INDICATE WIRE GAGE.
  