Plan Review Notes
Plan Review Notes For Permit 12020587
Permit Number 12020587
Review Stop M
Sequence Number 1
Notes
Date Text
2012-03-28 09:53:02PLANS DENIED
 1) PROVIDE A COMPLETE SET OF MECHANICAL PLANS.SECTION
 106.1.1 FBC 2007
 2) PROVIDE LOCATION OF MECHANICAL EQUIPMENT ON THE
 PLANS. SECTION 106.1.1
 3) PROVIDE MECHANICAL CONTRACTOR SIGNATURE ON THE
 APPLICATION.
 4) REFER TO SECTION 13-409.AB.3.3 DAMPER SHUTOFF
 CONTROL'S FLORIDA ENERGY CODE.
 5) REFER TO FLORIDA STATUTES CHAPTER 471 ENGINEERING
 407.003 QUALIFICATION FOR PRACTICE.