 PERMIT #12020587
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED AREAS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 DESIGN DOCUMENTS NEED TO INCLUDE THE SCOPE OF WORK FOR
 THE MODIFICATION OF THE EXISTING FIRE SPRINKLER AND
 FIRE ALARM SYSTEM. AT MINIMUM, PROVIDE FIRE ALARM
 INITIATING/NOTIFICATION APPLIANCE LOCATIONS AND
 INDICATE THE SPRINKLER HAZARD CLASSIFICATION WITH
 DESIGN DENSITY. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED DESIGN
 DOCUMENTS) FOR A SUB-PERMIT. SEPARATE PLANS AND PERMITS
 ARE REQUIRED FOR THE INSTALLATION OR MODIFICATION OF
 THE FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 FIRE RATED WALLS SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE/SMOKE BARRIER-PROTECT
 ALL OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PLANS DO NOT INDICATE A FIRE RATED SEPARATION BETWEEN
 ADJACENT TENANT. INDICATE THE OCCUPANY OF THE ADJACENT
 TENANT.
  
 EXIT SIGNS ARE DIRECTING OCCUPANTS TO PASS THROUGH
 DOCTOR'S OFFICES.
  