Plan Review Notes
Plan Review Notes For Permit 12020587
Permit Number 12020587
Review Stop E
Sequence Number 1
Notes
Date Text
2012-02-29 14:06:4612020587
 400 EXECUTIVE CENTER DR.
 RENOVATION SUITE #110
  
 REVISE THE ELECTRICAL PLAN TO INCLUDE THE REQUIREMENTS
 FOR WIRING IN PATIENT CARE AREAS OF ALL EXAM AND
 TREATMENT ROOMS. NEC 517.10
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
 PROVIDE A LIGHTING DENSITY CALCULATIONS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 PROVIDE EMERGENCY EGRESS LIGHTING. FBC 1006.1
 RECEPTACLES LOCATED WITHIN SIX FEET OF SINKS MUST BE
 GFCI PROTECTED. NEC 210.8
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  