Date |
Text |
2012-02-29 12:47:11 | 4801 DREHER TRAIL NORTH |
| PERMIT #12020414 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| SHEET LS-100: UPDATE THE CODE LIST TO REFERENCE THE |
| 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| WITH FLORIDA AMENDMENTS. |
| |
| DEMOLITION: TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| PROHIBITED EXCEPT IN DESIGNATED AREAS. ALL OTHER |
| DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. |
| |
| DEMOLITION: WHERE SMOKING IS PERMITTED, SAFE |
| RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| |
| GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY |
| THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH |
| DIXIE HIGHWAY. |
| |
| SHEET A-101: PROVIDE FIRE LANE SIGNAGE FOR EXISTING |
| DROP-OFF LANE. FIRE LANES SHALL BE MARKED WITH |
| FREESTANDING SIGNS READING, "FIRE LANE - NO PARKING BY |
| ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18" |
| WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A |
| MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE |
| SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW |
| AND BE SPACED A MAXIMUM OF 60 FEET APART. |
| |
| SHEET A-201: PROVIDE A 1-HOUR FIRE/SMOKE BARRIER FOR |
| THE RECEIVING/STORAGE ROOM #105 PER SECTION 12.7.5.2 OF |
| NFPA 101. PROTECT ALL OPENINGS AND PENETRATIONS. |
| |
| GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| GENERAL: FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 |
| OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON |
| DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| PANIC HARDWARE. |
| |
| GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| DOORS WITH EXIT SIGNS. |
| |
| GENERAL: POST "NO SMOKING" SIGNS IN ALL EXHIBIT ROOMS. |
| |
| GENERAL: AN EMERGENCY PLAN SHALL BE DEVELOPED AND |
| APPROVED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF |
| OCCUPANCY. |
| |
| SHEET F-002: PROVIDE LOCKABLE KNOX CAPS ON FIRE |
| DEPARTMENT CONNECTION. |
| |
| FIRE ALARM: A CERTIFICATE OF COMPLETION AND A THIRD |
| PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE |
| SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM |
| INSPECTION. |
| |
| WESLEY JOLIN |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| |