Date Text
2012-02-29 12:47:114801 DREHER TRAIL NORTH
 PERMIT #12020414
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS-100: UPDATE THE CODE LIST TO REFERENCE THE
 2010 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 DEMOLITION: TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED AREAS. ALL OTHER
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 DEMOLITION: WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING AND APPROVED BY
 THE OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH
 DIXIE HIGHWAY.
  
 SHEET A-101: PROVIDE FIRE LANE SIGNAGE FOR EXISTING
 DROP-OFF LANE. FIRE LANES SHALL BE MARKED WITH
 FREESTANDING SIGNS READING, "FIRE LANE - NO PARKING BY
 ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL BE 12" X 18"
 WITH A WHITE BACKGROUND AND RED LETTERS AND SHALL BE A
 MAXIMUM OF SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE
 SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW
 AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 SHEET A-201: PROVIDE A 1-HOUR FIRE/SMOKE BARRIER FOR
 THE RECEIVING/STORAGE ROOM #105 PER SECTION 12.7.5.2 OF
 NFPA 101. PROTECT ALL OPENINGS AND PENETRATIONS.
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 GENERAL: FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: POST "NO SMOKING" SIGNS IN ALL EXHIBIT ROOMS.
  
 GENERAL: AN EMERGENCY PLAN SHALL BE DEVELOPED AND
 APPROVED PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  
 SHEET F-002: PROVIDE LOCKABLE KNOX CAPS ON FIRE
 DEPARTMENT CONNECTION.
  
 FIRE ALARM: A CERTIFICATE OF COMPLETION AND A THIRD
 PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE
 SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM
 INSPECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  