Plan Review Notes
Plan Review Notes For Permit 12020414
Permit Number 12020414
Review Stop E
Sequence Number 1
Notes
Date Text
2012-03-05 14:48:30PANEL SCHEDULE WIRE AND CONDUIT SIZES DO NOT MATCH THE
 LOADS. NEC 215.5
 GFCI PROTECTION IS REQUIRED FOR THE ELECTRIC DRINKING
 FOUNTAIN. NEC 422.52
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOMS. NEC 110.22, 110.16
 PROVIDE DETAIL FOR THE ELECTRIC EQUIPMENT ROOM SHOWING
 SAFETY CLEARANCES. NEC 110.26
 A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING
 IS REQUIRED FOR SITE LIGHTING.
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR SECURITY,
 VOICE, DATA AND FIRE ALARM SYSTEMS.
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  