Plan Review Notes For Permit 12020414 |
Permit Number |
12020414 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-03-05 14:48:30 | PANEL SCHEDULE WIRE AND CONDUIT SIZES DO NOT MATCH THE | | LOADS. NEC 215.5 | | GFCI PROTECTION IS REQUIRED FOR THE ELECTRIC DRINKING | | FOUNTAIN. NEC 422.52 | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE | | REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL | | ROOMS. NEC 110.22, 110.16 | | PROVIDE DETAIL FOR THE ELECTRIC EQUIPMENT ROOM SHOWING | | SAFETY CLEARANCES. NEC 110.26 | | A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING | | IS REQUIRED FOR SITE LIGHTING. | | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR SECURITY, | | VOICE, DATA AND FIRE ALARM SYSTEMS. | | | | ROBERT LECKY | | ELECTRIC PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|