Plan Review Notes
Plan Review Notes For Permit 12020414
Permit Number 12020414
Review Stop B
Sequence Number 1
Notes
Date Text
2012-03-08 11:20:29BUILDING PLAN REVIEW
 PERMIT: 12020414
 ADD: 4801 DREHER TRAIL N
 CONT: TBD
 TEL: (561)###-####
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 BUILDING TYPE III-B
 FULLY SPRINKLERED
  
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-101 INDICATES DETAILS ON SHEET A-151
 1A) SHEET A-151 DETAIL # 1 INDICATES THE USE OF A
 PRE-MANUFACTURED ALUMINUM RAMP AND HANDRAIL NO DETAILS
 ARE PROVIDED FOR STRENGTH AN OR ACCESSIBILITY
 REQUIREMENTS
  
 1B) SHEET A-151 DETAIL 02 INDICATES A CONCRETE RAMP AND
 HANDRAIL THE PLANS DO NOT PROVIDE ENOUGH INFORMATION
 FOR THE ACCESSIBLE RAMP NOR STAIRS.
  
 1C) SHEET A-101 INDICATES A DETAIL 01/A151 WHICH REFERS
 TO DETAIL # 11/A-613. THE PLANS ARE NOT CLEAR AS TO IF
 THE HORIZONTAL AND VERTICAL CANOPY PIECES ARE TO BE
 SOLID OR DOES THE MATERIAL ALLOW WIND THROUGH THE
 MATERIAL. S-102 DOES INDICATE WITH NOTE 6 HIGHER
 PRESSURES FOR THIS CANOPY SECTION.
  
 2) SHEET A-101 THIS LOCATION IS IN A A-7 FLOOD ZONE,
 THE MINIMUM FINISH FLOOR OF 12.5?. THE FINISH FLOOR OF
 THE EXISTING BUILDING AND ADDITION IS INDICATED WELL
 ABOVE THIS HEIGHT BUT THE
 NEW EMERGENCY GENERATOR AND PAD AS WELL AS HV/AC
 EQUIPMENT PAD HEIGHTS ARE NOT PROVIDED. THESE EQUIPMENT
 PADS HAVE TO BE AT LEAST THE BASE FLOOD ELEVATION OF
 12.5 ? NGVD.
  
 3) LS-100 HEADING BUILDING SEPARATION INDICATES THE
 BUILDING SEPARATION WALLS FIRE WALLS TO BE 3HOUR RATED
 WALLS AS WELL AS LS-201, LS-202 & LS-203 WITH 2 HOUR
 OPENING PROTECTIVE?S.
  
 3A) PLEASE REVIEW 2007/09 FBC-B TABLE 705.4 FOOTNOTE C.
 FOR THE PURPOSES OF DETERMINING HEIGHT AND AREA IN
 ACCORDANCE WITH TABLE 503, FIRE WALLS DIVIDING
 BUILDINGS INTO SEPARATE BUILDINGS SHALL PROVIDE A
 4-HOUR FIRE-RESISTANCE RATING.
  
 3B) OPENING PROTECTIVES2007/09 FBC-B TABLE 715.4
 REQUIRES EITHER A 3 HOUR RATED FIRE DOOR AND FIRE
 SHUTTER ASSEMBLY. PLEASE NOTE THAT 715.3 DOES ALLOW FOR
 715.3 ALTERNATIVE METHODS FOR DETERMINING FIRE
 PROTECTION RATINGS. BASED ON THE FIRE EXPOSURE AND
 ACCEPTANCE CRITERIA SPECIFIED IN NFPA 252 OR NFPA 257.
 THE REQUIRED FIRE RESISTANCE OF AN OPENING PROTECTIVE
 SHALL BE PERMITTED TO BE ESTABLISHED BY ANY OF THE
 FOLLOWING METHODS OR PROCEDURES:
 1. DESIGNS DOCUMENTED IN APPROVED SOURCES.
 2. CALCULATIONS PERFORMED IN AN APPROVED MANNER.
 3B) 3. ENGINEERING ANALYSIS BASED ON A COMPARISON OF
 OPENING PROTECTIVE DESIGNS HAVING FIRE-PROTECTION
 RATINGS AS DETERMINED BY THE TEST PROCEDURES SET FORTH
 IN NFPA 252 OR NFPA 257.
 3B) 4. ALTERNATIVE PROTECTION METHODS AS ALLOWED BY
 SECTION 104.11.
  
 4) SHEET LS-201, LS-202 & LS-203 ALL SHOW THE NEW DECK
 AND ADA MODULAR RAMP AS PART OF THE MEANS OF EGRESS BUT
 THE PLANS DO NOT PROVIDE COMPLIANCE WITH THE EXIT
 DISCHARGE LEADING TO A PUBLIC WAY. FBC-B 1024.1.
 11-4.1.3(8)(II).
  
 5) SHEET A-650 INDICATES WALL TYPES BUT NOTE # 3
 INDICATES REFER TO LIFE SAFETY PLANS FOR LOCATION AND
 FULL EXTENT OF FIRE AND SMOKE RATED ASSEMBLIES. COMMENT
 # 3 DEALS WITH THE 4 HR RATED FIRE WALL THAT SEPARATES
 THE TWO BUILDINGS BUT THE PLANS DO NOT PROVIDE FOR FIRE
 RATING FOR THE FIRST FOUR FEET PAST WHERE THE EXTERIOR
 WALL INTERSECTS, SEE FBC-B 705.5.1.
  
 6A) SHEET LS-201, LS-202 & LS-203 DOES NOT PROVIDE FOR
 ANY RATINGS OF OTHER WALLS. FBC-B TABLE 508.2 FOR
 STORAGE ROOMS WITH FULLY SPRINKLERED BUILDINGS STILL
 REQUIRE THE WALLS TO BE A SMOKE PARTITION SEE FBC- B
 508.2.2.1.
 THE PARTITIONS SHALL EXTEND FROM THE FLOOR TO THE
 UNDERSIDE OF THE FIRE-RESISTANCE-RATED FLOOR/CEILING
 ASSEMBLY OR FIRE-RESISTANCE-RATED ROOF/CEILING ASSEMBLY
 ABOVE OR TO THE UNDERSIDE OF THE FLOOR OR ROOF
 SHEATHING, OR SUB DECK ABOVE.
  
 6B) SHEET A-251 DETAILS 03, 08 & 10 ARE ALL DETAILS
 INDICATING CUT SECTIONS THROUGH THE 4 HOUR FIRE RATED
 WALL, PLEASE PROVIDE AN ASSEMBLY RATING FOR SUCH WALL.
 SHEET A-611 DETAIL # 4
 DEPICTS TWO SEPARATE WALL DETAILS DETAIL FOUND ON A-451
 DETAIL # 5 DOES SHOW ROOF HEIGHTS AT TWO DIFFERENT
 HEIGHTS. PLEASE PROVIDE WALL RATING OF PARAPET WALL.
 705.6.1.
  
 7) STRUCTURAL SHEET S-2.1122 INDICATES THE USE OF
 EPICORE ER2R NOTE # 2 INDICATES 18 GAGE STEEL SUPPORTED
 BY CSTELLATED CELLULAR BEAMS. THE ESR-2047 REPORT ON
 THIS SYSTEM PROVIDES
 TABLES AND SPANS FOR THIS SYSTEM BEING USED WITH A
 POURED 4 INCH CONCRETE DECK SYSTEM. THE DETAIL SHEETS
 A-613 INDICATE THE USE OF ONLY RIGID FOAM AND A BUILT
 UP SYSTEM. HOW FAR CAN THIS STEEL DECKING SPAN WITHOUT
 A CONCRETE DECK, NOTE ROOFING PRODUCT APPROVALS MAY
 HAVE SPAN LIMITATIONS ( SPACING CENTER TO CENTER).
 ADDITIONAL INFORMATION REQUIRED. 106.1.2.
  
 8) PLEASE PROVIDE SOILS REPORTS BY NORARSE & ASSOCIATES
 DATED 12/07/2011, FBC-B 1802.6.
  
 9) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10)THE PRESSURES FOUND IN THE STRUCTURAL SHEETS ARE
 CORRECT, THESE ITEMS, PRODUCT APPROVALS CAN BE REVIEWED
 UNDER A REVISION WITH ASSOCIATED REVIEW AND FEES OR
 ONCE A CONTRACTOR HAS BEEN PICKED THEY COME IN AT THAT
 TIME. NOTE PERMITS THAT ARE READY FOR ISSUANCE AND THE
 CONTRACTOR BRINGS IN THE PRODUCT APPROVALS FOR A FIRST
 REVIEW MAY DELAY THE ISSUANCE OF THE PERMIT .
 FBC-B 1609 COMPONENTS & CLADDING, FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS GLAZED EXT DOORS, METAL EXT,
 OVERHEAD GARAGE STYLE & ROOF HATCH TYPE DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFING NOA
 10-0125.05 SEE DECK LIMITATION # 2 DECK SPANS EVERY 5
 FT.
 (G) PRE-ENGINEERED A/C STANDS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676