2012-02-27 14:03:50 | BUILDING PLAN REVIEW |
| PERMIT: 12020411 |
| ADD: 1025 7TH ST. |
| CONT: NORTH COUNTY PLUMBING |
| TEL: (561)625-9414 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) 2007/09 FBC-B CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| THE PLANS DO NOT PROVIDE DETAILS AS TO LOCATION, |
| FIXTURE LOCATION FROM WALLS, CENTER LINE TO CENTER LINE |
| OF FIXTURES, DEPTH OF STALLS, SIZE OF DOORS FOR THE |
| STALLS NOR THE SIZE AND LOCATION OF THE RESTROOM ENTRY |
| DOOR. |
| |
| 2) PLANS ARE NOT DRAWN TO SCALE MAKING IT DIFFICULT TO |
| DETERMINE, IF THE DOOR THAT SWINGS INTO THE RESTROOM |
| WILL LEAVE ROOM INFRONT OF THE LAVOTORY. PLEASE REVIEW |
| FBC-P 405.3.1 FOR REQUIRED CLEARENCE IN FRONT OF THE |
| LAVATORIES AND THE RIGHT WATER CLOSET, IT APPEARS THE |
| DOOR MAY BUMP INTO THE WATER CLOSET? |
| |
| 3) PLEASE PROVIDE ADDITIONAL INFORMATION FOR WHAT |
| APPEARS TO BE STALL PARTITIONS, HOW FAR ARE THEY OFF |
| THE FLOOR, AND WHAT WILL THEIR HEIGHT BE? HOW WILL THEY |
| BE ANCHORED INTO THE WALL. |
| |
| 4) PLEASE INDICATE COMPLIANCE WITH 2007/09 FBC-B : |
| 1210.1 FLOORS. IN OTHER THAN DWELLING UNITS, TOILET AND |
| BATHING ROOM FLOORS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE WALLS |
| AT LEAST 6 INCHES (152 MM). |
| |
| 1210.2 WALLS. WALLS WITHIN 2 FEET (610 MM) OF URINALS |
| AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) |
| ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, |
| THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE |
| THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| |
| 5) IT APPEARS THAT THE PLUMBING CONTRACTOR IS TAKING |
| THE EXEMPTION UNDER 471.003.(2)(B) IN DESIGNING THEIR |
| OWN WORK. A CBCOR CGC WILL NEED TO SIGN ONTO THE PERMIT |
| FOR THE BUILDING PORTION OF THE PLANS AND WILL NEED TO |
| REVIEW 489.229(1)(C) AS TO WHO MAY DRAW PLANS FOR |
| PUBLIC USE. |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |