2012-03-09 09:53:18FBC FUEL GAS REVIEW #2
 DENIED:
  
 REVISION SUBMITTED FOR NON-ISSUED GAS PERMIT.
 ORIGINAL GAS REVIEW WAS DENIED. DENIED COMMENTS FRON
 REVIEW #1 BELOW:
  
 FBC FUEL GAS 2007 REVIEW #1
  
 1. SUBMITTED PLANS ARE COPIES OF ENGINEER SEALED PLANS.
 PLEASE SUBMIT ISOMETRIC DRAWINGS THAT HAVE THE JOB
 ADDRESS, THE COMPANY NAME AND SIGNATURE.
  
 2. THE FOLLOWING INFORMATION WILL BE REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2007 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL).
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2007 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35)
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2007 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4)
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR