2012-02-23 17:55:47RESIDENTIAL (R3) ALTERATION PLUMBING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLUMBING FIXTURES ARE NOT PROPERLY VENTED. SANITARY
 RISER DIAGRAM 2/E1 ON SHEET E1 SHOWS NO VENT FOR THE
 WATER CLOSET, TUB AND SHOWER. IN HORIZONTAL WET-VENT
 SYSTEMS, NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN
 SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE
 DRAIN CONNECTION. SEE SEC. P3108.2.
  
 2- CLEARLY SPECIFY VENT SIZES AS REQUIRED BY SEC.
 P3108.3.
  
 3- REVISE SANITARY RISER DIAGRAM 2/E1. EACH FIXTURE
 DRAIN SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL
 BRANCH BEING WET VENTED OR SHALL HAVE A DRY VENT. SEC.
 P3108.1.
 ALSO, INFORMATION SHOWN ON FLOOR PLAN 1/E1 DOESN'T
 MATCH INFORMATION SHOWN ON SANITARY RISER DIAGRAM 2/E1.
  
 ***NOTE: PLUMBING RISER DIAGRAM MAY BE DRAWN BY THE
 LICENSED PLUMBING CONTRACTOR DOING THE JOB. IF DOING
 SO, THEN PLUMBING CONTRACTOR TO WRITE NAME, LICENSE
 NUMBER AND SIGN THE DRAWING.
  
 4- SHEET E1: DETAIL 4/E1: TRAP GUARD ON FLOOR DRAIN IS
 NOT ALLOWED. TRAPS FOR FLOOR DRAINS SHALL BE FITTED
 WITH A TRAP PRIMER OR SHALL BE OF THE DEEP SEAL DESIGN
 AS REQUIRED BY SEC. P3201.2.
  
  