2012-02-09 14:59:21 | ***PROVISO*** | | | | 1. PLAN CLAIMS EXTERIOR WINDOW OPENINGS OF 40 SQ. FT. | | FOR NATURAL VENTILATION. THE SIZE OF THE OPENABLE | | WINDOW AREA SHALL BE VERIFIED IN THE FIELD. FBC-M | | SECTION 402. | | | | 2. TWO NEW 14X10 DUCTS ARE SHOWN PENETRATING AN | | EXISTING TENANT SEPARATION WALL. FIRE DAMPERS ARE | | REQUIRED AT THESE PENETRATIONS PER FBC-M 607.5.3 AND | | SHALL BE SHOWN ON THE PLANS PER FBC-M 607.8. REVISION | | REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|