Plan Review Notes For Permit 12020002 |
Permit Number |
12020002 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-02-02 16:32:15 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. PROVIDE A PLAN SHOWING PROPOSED DOOR LOCATION, DOOR | | SWING, FIRE RESISTANCE REQUIRED, AND WHETHER OR NOT | | PANIC BARS ARE TO BE INCLUDED IN THE INSTALLATION. | | PROVIDE INFORMATION REGARDING THE METER ROOM TO SHOW | | WHETHER PANIC DEVICES ARE REQUIRED, SEE FBC1008.1.9. | | ALL INFORMATION REQUIRED TO SHOW CODE COMPLIANCE IS TO | | BE INCLUDED ON THE PLAN. THE CONTRACT DOES NOT SHOW | | THAT PANIC BARS ARE PROPOSED, PLEASE INCLUDE ENOUGH | | INFORMATION ON THE PLAN TO SHOW WHY THIS INSTALLATION | | IS EXEMPT. THE CONTRACT SHOWS A 90 MINUTE DOOR | | PROPOSED; PLEASE INCLUDE THIS INFORMATION ON THE PLAN. | | | | 2. IF THIS IS AN EXTERIOR DOOR, AN ENGINEER IS TO | | SPECIFY DESIGN PRESSURES, FBC1609. | | | | |
|