Plan Review Notes For Permit 12010664 |
Permit Number |
12010664 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-02-07 15:19:57 | 1016 CLARE AVENUE - SUITE #5 | | PERMIT #12010664 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO - SUBMIT REVISION***** | | | | FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS | | TO EACH FIRE ALARM DEVICE ON THE SYSTEM. | | | | THE QUALIFIED SYSTEM DESIGNER SHALL BE IDENTIFIED ON | | THE PLANS. | | | | THE TWO SPEAKER/STROBE APPLIANCES LOCATED WEST OF STAIR | | #2 APPEAR TO BE LOCATED TOO FAR FROM THE WALL NEAR | | COLUMN LINE 3. | | | | INDICATE THE CANDELA SETTING OF THE VISUAL APPLIANCES. | | | | INDICATE THE WIRE SIZES TO BE INSTALLED. | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | |
|