2012-02-07 15:19:571016 CLARE AVENUE - SUITE #5
 PERMIT #12010664
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBERS/LETTERS
 TO EACH FIRE ALARM DEVICE ON THE SYSTEM.
  
 THE QUALIFIED SYSTEM DESIGNER SHALL BE IDENTIFIED ON
 THE PLANS.
  
 THE TWO SPEAKER/STROBE APPLIANCES LOCATED WEST OF STAIR
 #2 APPEAR TO BE LOCATED TOO FAR FROM THE WALL NEAR
 COLUMN LINE 3.
  
 INDICATE THE CANDELA SETTING OF THE VISUAL APPLIANCES.
  
 INDICATE THE WIRE SIZES TO BE INSTALLED.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  