| BUILDING PLAN REVIEW |
| PERMIT: 12010663 |
| ADD: 801 S OLIVE AVE # 708 |
| CONT: NEW CITY CONSTRUCTION |
| TEL: (561)541-6160 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH |
| THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| BUILDING. |
| |
| CODE SUMMARY/ RED LINED: |
| TYPE OF CONSTURCTION : IA |
| OCCUPANCY TYPE: R2 |
| |
| BUILDING PROVISO: |
| |
| 1) MISSING FLOOR SOUND PROOFING DOCUMENTATION, |
| CONTRACTOR TO HAVE AT JOBSITE FOR INSPECTOR TO BRING |
| IN FOR THE BUILDING DEPARTMENT CITY FILES. |
| 2007/09 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT |
| INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. |
| |
| 2) 2509.2 BASE FOR TILE. CEMENT, FIBER-CEMENT OR GLASS |
| MAT GYPSUM BACKERS IN COMPLIANCE WITH ASTM |
| C 1178, C 1288 OR C 1325 AND INSTALLED IN ACCORDANCE |
| WITH MANUFACTURER RECOMMENDATIONS SHALL BE |
| USED AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS |
| AND WALL AND CEILING PANELS IN SHOWER AREAS. |
| WATER-RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A |
| BASE FOR TILE IN WATER CLOSET COMPARTMENT |
| WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM |
| C 840 AND MANUFACTURER RECOMMENDATIONS. |
| REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| |