2012-02-10 13:52:01FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. SHEETS P2.0, P2.1, P2.2 THE RESTROOM DRAWINGS ARE
 MISSING THE CURCUIT VENT.
 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION
 SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE
 DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905.
 THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE
 OF ANY SOIL OR WASTE.
  
 2. SHEET P2.0 THE SANITARY BRANCH FOR THE ELEVATOR PUMP
 IS NOT VENTED.
  
 3. PROTECTION FROM OIL IN THE SANITARY SYSTEM WILL BE
 REQUIRED FOR THE ELEVATOR SUMP. AN APPROVED ELECTRONIC
 SENSOR SYSTEM WOULD BE OK.
  
 ***NOTE***
 IRRIGATION WILL NOT BE PART OF THIS REVIEW. SEPARATE
 APPLICATION, PLAN, FEES, PERMIT REQUIRED.
  