Plan Review Notes For Permit 12010646 |
Permit Number |
12010646 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-02-10 13:52:01 | FBC PLUMBING 2007 REVIEW #1 | | DENIED: | | | | 1. SHEETS P2.0, P2.1, P2.2 THE RESTROOM DRAWINGS ARE | | MISSING THE CURCUIT VENT. | | 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION | | SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE | | DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH | | AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905. | | THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE | | OF ANY SOIL OR WASTE. | | | | 2. SHEET P2.0 THE SANITARY BRANCH FOR THE ELEVATOR PUMP | | IS NOT VENTED. | | | | 3. PROTECTION FROM OIL IN THE SANITARY SYSTEM WILL BE | | REQUIRED FOR THE ELEVATOR SUMP. AN APPROVED ELECTRONIC | | SENSOR SYSTEM WOULD BE OK. | | | | ***NOTE*** | | IRRIGATION WILL NOT BE PART OF THIS REVIEW. SEPARATE | | APPLICATION, PLAN, FEES, PERMIT REQUIRED. | | |
|