2012-02-13 15:21:29315 SOUTH FLAGLER DRIVE
 PERMIT #12010646
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **SHEET A0.0: PLAN STATES CERTAIN STAIRS WILL BE OUT OF
 SERVICE AND BUILDING OCCUPANTS WILL NEED TO
 "RE-DIRECTED" TO IN-SERVICE STAIRS DURING DIFFERENT
 PHASES OF CONSTRUCTION. SUBMIT ADDITIONAL INFORMATION
 AS TO HOW THE EXITING PLAN WILL BE EXECUTED AND MANAGED
 WITH REGARDS TO BUILDING EMERGENCY PLANS, EXISTING EXIT
 SIGN LOCATIONS, TEMPORARY SIGNAGE, STAFF, OCCUPANTS,
 VISITORS ETC.
  
 SHEET A1.11: PROVIDE NON-COMBUSTIBLE 18" DEEP DRAFT
 STOPS AROUND FLOOR OPENING. PROVIDE CLOSELY SPACED
 SPRINKLERS AROUND FLOOR OPENING.
  
 SHEET FP0.1: THE CONSTRUCTION DOCUMENTS SIGNED/SEALED
 BY THE ENGINEER, ESTABLISH R. DAVENPORT AS THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION DESIGN; THEREFORE,
 THE FIRE SPRINKLER SHOP DRAWINGS SHALL NOT BE SEALED.
  
 SHEET FP1.1: PROVIDE NON-COMBUSTIBLE 18" DEEP DRAFT
 STOPS AROUND FLOOR OPENING. PROVIDE CLOSELY SPACED
 SPRINKLERS AROUND FLOOR OPENING.
  
  
 GENERAL
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
  
 DEMOLITION/CONSTRUCTION
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 SMOKING SHALL BE PROHIBITED THROUGHOUT THE DEMOLITION
 AREAS. "NO SMOKING" SIGNS SHALL BE POSTED THROUGHOUT.
  
 SMOKING SHALL BE PERMITTED ONLY IN DESIGNATED AREAS.
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  