Plan Review Notes For Permit 12010646 |
Permit Number |
12010646 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-02-13 11:25:00 | 12010646 | | 315 S. FLAGLER DRIVE | | RENOVATION TO LOURDES-NOREEN MCKEAN RESIDENCE | | | | VERIFY NOTE 4: 2/0 AL LIMITED TO 135 AMPERES? NEC T. | | 310.16 | | VERIFY THE 150 KVA TRANSFORMER IS LOCATED WITHIN A | | FIRE-RESISTANT ROOM WITH A ONE HOUR FIRE RATING OR | | COMPLIES WITH THE NEC EXCEPTIONS. NEC 450.21 (B) | | VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND | | GROUPED IN ONE LOCATION. NEC 230 | | EACH STRUCTURE OR BUILDING SHALL BE SUPPLIED BY ONLY | | ONE FEEDER. FEEDER TO PANEL GH1 APPEARS TO ORIGINATE | | FROM ANOTHER SERVICE IN ANOTHER BUILDING. NEC 225.25 | | A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR | | EQUIPMENT ROOM. NEC 620.23 | | KITCHEN PANELS REQUIRE CLEAR UNOBSTRUCTED DEDICATED | | WORKING SPACE. NEC 110.26 | | INDICATE THE FEEDER CONDUCTOR SIZES FOR THE KITCHEN | | PANELS. NEC T. 310.16 | | INDICATE THE OVERCURRENT PROTECTION REQUIRED FOR THE | | TRANSFORMER FEEDER AT PANELBOARD EQH1. NEC 215.5 | | VERIFY NUMBER 2 AL RATED AT 90 AMPERES IS ADEQUATE TO | | CARRY THE NEUTRAL LOAD AT PANEL BOARD KN1. NEC 220.61 | | FEEDER CONDUCTORS TO THE 150 KVA TRANSFORMER APPEAR TO | | BE UNDER SIZED. NEC 215.2 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|