2012-01-30 11:50:59SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED.
 ADDITIONAL INFORMATION MAY BE NEEDED. PLEASE PROVIDE
 THE FOLLOWING:
  
 INDICATE THE SIZE AND LOCATION OF THE ELECTRICAL PANEL.
 PROVIDE A PANEL SCHEDULE AND SUMMARY LOAD CALCULATION.
 SHOW THE SERVICE LOCATION, FEEDER SIZE AND EXISTING
 MAIN BREAKER. INCLUDE A FLOOR PLAN SHOWING THE LOCATION
 OF ALL NEW AND EXISTING OUTLETS INCLUDING LIGHTING. NEC
 215.5
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 VERIFY THE BATHROOM RECEPTACLES ARE GFCI PROTECTED. NEC
 210.8
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE FRONT AND BACK. NEC 210.70
  