Plan Review Notes For Permit 12010467 |
Permit Number |
12010467 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-02-15 10:53:14 | 701 NORTHPOINT PARKWAY - SUITE #500 | | PERMIT #12010467 | | MASTER #11110281 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE TWO EXISTING SPEAKER-STROBE APPLIANCES IN THE MAIN | | CORRIDOR DO NOT PROVIDE ADEQUATE VISUAL COVERAGE PER | | NFPA 72. | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE |
|