2012-01-27 13:08:47701 NORTHPOINT PARKWAY - SUITE #500
 PERMIT #12010467
 MASTER #11110281
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE ROOM NAMES ON PLANS AND INDICATE THE LOCATION
 OF EXISTING FIRE ALARM DEVICES TO VERIFY SUFFICIENT
 COVERAGE EXISTS FOR THE ENTIRE FLOOR.
  
 THE QUALIFIED SYSTEM DESIGNER SHALL BE IDENTIFIED ON
 THE PLANS.
  
 INDICATE THE ADDRESS OF THE NEW DUCT SMOKE DETECTOR.
  
 PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL
 BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  