Plan Review Notes
Plan Review Notes For Permit 12010464
Permit Number 12010464
Review Stop E
Sequence Number 1
Notes
Date Text
2012-01-25 10:59:5412010464
 508 NORTHWOOD RD.
 NEW SERVICE
  
 SUBMIT AN AVAILABLE FAULT CURRENT LETTER FROM FPL.
 INDICATE THE EQUIPMENT HAS A SUFFICIENT INTERRUPTING
 RATING. NEC 110.9
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31
  
 PROVIDE FOR ELECTRICAL SYSTEM GROUNDING. NEC 250.20
  
 PROVIDE AND GROUP ALL SERVICE DISCONNECTS IN ONE
 LOCATION. NEC 230.70, 230.2
  
 INDICATE THE HEIGHT OF THE MAST AND SERVICE LATERAL
 CONDUCTORS. NEC 230.24
  
 PROVIDE AN INTERSYSTEM BONDING TERMINAL. NEC 250.94
  
 THWN REQUIRED FOR WET LOCATIONS. NEC T. 310.13 (A)
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  