Plan Review Notes For Permit 12010464 |
Permit Number |
12010464 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-25 10:59:54 | 12010464 | | 508 NORTHWOOD RD. | | NEW SERVICE | | | | SUBMIT AN AVAILABLE FAULT CURRENT LETTER FROM FPL. | | INDICATE THE EQUIPMENT HAS A SUFFICIENT INTERRUPTING | | RATING. NEC 110.9 | | | | PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31 | | | | PROVIDE FOR ELECTRICAL SYSTEM GROUNDING. NEC 250.20 | | | | PROVIDE AND GROUP ALL SERVICE DISCONNECTS IN ONE | | LOCATION. NEC 230.70, 230.2 | | | | INDICATE THE HEIGHT OF THE MAST AND SERVICE LATERAL | | CONDUCTORS. NEC 230.24 | | | | PROVIDE AN INTERSYSTEM BONDING TERMINAL. NEC 250.94 | | | | THWN REQUIRED FOR WET LOCATIONS. NEC T. 310.13 (A) | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|