Plan Review Notes For Permit 12010450 |
Permit Number |
12010450 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-02-14 11:28:34 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY MECHANICAL | | | | 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS | | AS REQUIRED BY FBCR M1401.3. | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE WITH THE MODEL NUMBERS | | ON THE MECHANICAL PLANS. FBCR M13.3.1 | | | | 3) A SERVICE DISCONNECT, SWITCH CONTROLLED LUMINAIRE | | AND RECEPTACLE OUTLET ARE REQUIRED AT THE HVAC | | EQUIPMENT. SHOW COMPLIANCE WITH FBCR M1305.1.3.1. | | | | 4) SHOW COMPLIANCE WITH FBCR M1305.1.3 FOR ACCESS TO | | APPLIANCES IN ATTICS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|