2012-02-15 09:12:34 | 2007 FBC W/2009 REVISIONS |
| |
| DENIED BY BUILDING |
| |
| 1) PLEASE REVISE THE DESIGN CRITERIA ON SHEET 1.1 TO |
| REFERENCE ASCE 7-05. FBCR CHAPTER 43. |
| |
| 2) UNDER THE EXISTING BUILDING NOTE ON SHEET 1.1 PLEASE |
| CHANGE FROM 2004 FBC TO THE CODE IN EFFECT WHICH IS THE |
| 2007 FBC. |
| |
| 3) SUBMIT TWO SETS OF ENERGY CALCULATIONS AS REQUIRED |
| BY THE 2007 FBCR ENERGY GLITCH AMENDMENTS N 1100. |
| |
| 4) THE POCKET DOOR TO THE ROOM CONTAINING THE WATER |
| CLOSET IS REQUIRED TO HAVE A 29" CLEAR OPENING. FL |
| ACCESSIBILITY CODE SECTION 11-4.22.2 |
| |
| 5) ON SHEET 4.1 THE PLAN SPECIFIES ALL EXTERIOR DOORS |
| TO BE THERMA-TRU WITH CLEAR GLASS, HOWEVER, THE PRODUCT |
| APPROVALS THAT WERE SUBMITTED ARE FROM MASONITE |
| INTERNATIONAL. PLEASE CLARIFY. CITY AMENDMENTS 106.1.1 |
| |
| 6) NOTE (1) FOR THE TRUSS ANCHOR SCHEDULE ON SHEET 5.1 |
| SAYS TO SEE ANCHOR DETAILS ON S-4 FOR THE REQUIRED |
| FASTENERS. THERE IS NO SHEET S-4. THE DETAILS ARE ON |
| SHEET 6.2. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 |
| |
| 7) THE FLORIDA PRODUCT APPROVAL NUMBERS AND THE ANCHOR |
| CAPACITIES LISTED IN THE TRUSS ANCHOR SCHEDULE ON SHEET |
| 5.1 ARE NOT CORRECT. PLEASE REVISE. DCA RULE 9N-3 & FBC |
| R802.1.6.5 |
| |
| 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| AMENDMENTS 106.3.3 |
| |
| 9) PLEASE UPDATE THE DESIGN CRITERIA IN THE WINDOW AND |
| DOOR PRESSURE TABLE ON SHEET 6.2 TO THE 2007 FBC AND |
| ASCE 7-05. FBCR CHAPTER 43 |
| |
| 10) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE |
| DOUBLE OUTSWING GLAZED DOORS HAS A MAXIMUM DESIGN |
| PRESSURE OF - 55 PSF AND THE PLAN REQUIRES -58 PSF |
| ACCORDING TO THE TABLE ON SHEET 6.2. PLEASE PROVIDE |
| PRODUCT WITH ADEQUATE DESIGN PRESSURES. DCA RULE 9N-3 |
| |
| 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE SIX |
| PANEL METAL FRONT DOOR THAT IS SPECIFIED ON THE PLANS. |
| DCA RULE 9N-3 |
| |
| 12) PLEASE SUBMIT A RESPONSE LETTER THAT INDICATES HOW |
| EACH OF THE REVIEW COMMENTS WAS ADDRESSED. |
| |