Plan Review Notes For Permit 12010420 |
Permit Number |
12010420 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-24 17:57:37 | 12010418 | | 3031 OKEECHOBEE BLVD | | SOLAR PHOTOVOLTAIC SYSTEM | | | | PROVIDE A FLOOR PLAN SHOWING THE RELATIVE LOCATION OF | | THE SYSTEM DEVICES AND OVERCURRENT DEVICES. | | PHOTOVOLTAIC DISCONNECTING MEANS SHALL BE INSTALLED AT | | A READILY ACCESSIBLE LOCATION NEAREST THE POINT OF | | ENTRANCE OF THE SYSTEM CONDUCTORS. NEC 690.14 | | | | INDICATE THE TYPE OF CONDUIT SYSTEM PROPOSED FOR ALL | | AREAS. NEC 690.31 (A) 690.31(E) | | | | VERIFY THE SELECTED EQUIPMENT ROOMS HAVE ADEQUATE | | SAFETY CLEARANCES FOR THE PHOTOVOLTAIC EQUIPMENT. NEC | | 110.26 | | | | SAFETY AND WARNING LABELS PREFERABLY RED IN COLOR ARE | | REQUIRED FOR THE VARIOUS PHOTOVOLTAIC SYSTEM | | COMPONENTS, RACEWAYS, JUNCTION BOXES, INVERTERS, | | COMBINER, SAFETY SWITCH, MDP, INCLUDING THE MAIN | | ELECTRICAL SERVICE AND METER. LABELS ARE TO BE | | PERMANENT. LABELS LOCATED OUTSIDE ARE TO BE SUNLIGHT | | AND WEATHER RESISTANT. NEC 690.53, 690.54, 690.56(B), | | 690.5(C), 690.35(F), 690.14, 690.17, 690.31(E) (3), | | 690.4(F) | | | | PROVIDE AN UPDATED VALUE FOR THE WORK WHICH INCLUDES | | ALL DEVICES AND EQUIPMENT. | | | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|