Plan Review Notes
Plan Review Notes For Permit 12010420
Permit Number 12010420
Review Stop E
Sequence Number 1
Notes
Date Text
2012-01-24 17:57:3712010418
 3031 OKEECHOBEE BLVD
 SOLAR PHOTOVOLTAIC SYSTEM
  
 PROVIDE A FLOOR PLAN SHOWING THE RELATIVE LOCATION OF
 THE SYSTEM DEVICES AND OVERCURRENT DEVICES.
 PHOTOVOLTAIC DISCONNECTING MEANS SHALL BE INSTALLED AT
 A READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE SYSTEM CONDUCTORS. NEC 690.14
  
 INDICATE THE TYPE OF CONDUIT SYSTEM PROPOSED FOR ALL
 AREAS. NEC 690.31 (A) 690.31(E)
  
 VERIFY THE SELECTED EQUIPMENT ROOMS HAVE ADEQUATE
 SAFETY CLEARANCES FOR THE PHOTOVOLTAIC EQUIPMENT. NEC
 110.26
  
 SAFETY AND WARNING LABELS PREFERABLY RED IN COLOR ARE
 REQUIRED FOR THE VARIOUS PHOTOVOLTAIC SYSTEM
 COMPONENTS, RACEWAYS, JUNCTION BOXES, INVERTERS,
 COMBINER, SAFETY SWITCH, MDP, INCLUDING THE MAIN
 ELECTRICAL SERVICE AND METER. LABELS ARE TO BE
 PERMANENT. LABELS LOCATED OUTSIDE ARE TO BE SUNLIGHT
 AND WEATHER RESISTANT. NEC 690.53, 690.54, 690.56(B),
 690.5(C), 690.35(F), 690.14, 690.17, 690.31(E) (3),
 690.4(F)
  
 PROVIDE AN UPDATED VALUE FOR THE WORK WHICH INCLUDES
 ALL DEVICES AND EQUIPMENT.
  
  