| 1ST REVIEW |
| ACTION: DENIED |
| 1) SHEET PV?8 STRUCTURAL SHEET INDICATES THIS TO BE IN |
| A B EXPOSURE WHILE TO THE NORTH THERE IS A CLEAR PATH |
| OVER 150 FEET WIDE AND 600 FEET LONG WHICH MAKES THIS A |
| EXPOSURE C?TYPE WITH THE INCREASED PRESSURES. FBC?B |
| 1609.4.3 EXPOSURE C/ AND ADJUSTMENT FACTOR OF 1.35 @ AN |
| ELEVATION OF 25 FT. |
| 2) PLEASE PROVIDE A ROOF PLAN WITH THE LOCATION OF THE |
| SOLAR PHOTOVOLTAIC PANELS INDICATE WHICH PANELS ARE |
| LOCATED IN ROOF ZONES 1, 2 & 3 WITH THE ASSOCIATED |
| PRESSURES. |
| 3) THE STRUCTURAL PLANS DO NOT PROVIDE THE TYPE OF |
| ANCHORS OR SIZE OF ANCHOR TO BE USED IN THE |
| INSTALLATION TO THE ROOF DECK, NOR DOES THE PLAN |
| INDICATE THE TYPE |
| OF ROOF DECK THESE ANCHORS ARE BEING INSTALLED IN. THE |
| PLANS INDICATE A PULL STRENGTH PER ANCHOR POINT BUT |
| AGAIN WHAT TYPE OF MATERIAL IS THIS DESIGN ANCHORED TO? |
| ADDITIONAL INFORMATION REQUIRED, MOMENT OF OVERTURNING, |
| FBC?B 1609. |
| |