Plan Review Notes
Plan Review Notes For Permit 12010420
Permit Number 12010420
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-24 17:59:50 
 PERMIT: 12010419
 ADDRESS: 3101 OKEECHOBEE BLVD
 CONT: DREAMWORKS ELECTRICAL SERVICES
 TEL: (772)341?9818
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 1ST REVIEW
 ACTION: DENIED
 1) SHEET PV?8 STRUCTURAL SHEET INDICATES THIS TO BE IN
 A B EXPOSURE WHILE TO THE NORTH THERE IS A CLEAR PATH
 OVER 150 FEET WIDE AND 600 FEET LONG WHICH MAKES THIS A
 EXPOSURE C?TYPE WITH THE INCREASED PRESSURES. FBC?B
 1609.4.3 EXPOSURE C/ AND ADJUSTMENT FACTOR OF 1.35 @ AN
 ELEVATION OF 25 FT.
 2) PLEASE PROVIDE A ROOF PLAN WITH THE LOCATION OF THE
 SOLAR PHOTOVOLTAIC PANELS INDICATE WHICH PANELS ARE
 LOCATED IN ROOF ZONES 1, 2 & 3 WITH THE ASSOCIATED
 PRESSURES.
 3) THE STRUCTURAL PLANS DO NOT PROVIDE THE TYPE OF
 ANCHORS OR SIZE OF ANCHOR TO BE USED IN THE
 INSTALLATION TO THE ROOF DECK, NOR DOES THE PLAN
 INDICATE THE TYPE
 OF ROOF DECK THESE ANCHORS ARE BEING INSTALLED IN. THE
 PLANS INDICATE A PULL STRENGTH PER ANCHOR POINT BUT
 AGAIN WHAT TYPE OF MATERIAL IS THIS DESIGN ANCHORED TO?
 ADDITIONAL INFORMATION REQUIRED, MOMENT OF OVERTURNING,
 FBC?B 1609.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561?805?6715
 FAX: 561?805?6676
 E?MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved