2012-06-20 11:11:562007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE CONCRETE BEAM (B-2) AT THE 10 FT WIDE GARAGE
 DOOR OPENING IS NOT LISTED IN THE BEAM & LINTEL DETAILS
 ON SHEET S1.2 AND THE BEAM SCHEDULE HAS BEEN REMOVED.
 PLEASE PROVIDE DETAIL FOR THIS BEAM. CITY AMENDMENTS
 107.2.1
  
 2) THE NOTE ON SHEET S1.3 SPECIFIES 8D SHANK NAILS FOR
 FASTENING THE ROOF SHEATHING . FBC R803.2.3.1 REQUIRES
 RING SHANK NAILS. PLEASE CORRECT.
  
 3) SPECIFY THE ROOF UPLIFT PRESSURES IN THE CHART ON
 SHEET S1.3. FBC R301.2.1
  
 4) THE PLANS APPEAR TO SHOW A NON-VENTED ATTIC AND THE
 ENERGY CALCULATIONS SPECIFY A VENTED ATTIC. PLEASE
 CORRECT. CITY AMENDMENTS 107.2.1
  
 5) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE USED IN THE
 NON-VENTED ATTIC. FBC R316.3
  
 6) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 7) SEVERAL OF THE PRODUCT APPROVALS HAVE BEEN
 SUPERSEDED OR ARE EXPIRED. PLEASE REVIEW ALL TO MAKE
 SURE THEY ARE CURRENT. DCA RULE 9N-3
  
 8) SPECIFY THE ROOF & FLOOR TRUSS DESIGN LIVE AND DEAD
 LOADS ON THE PLANS. FBC R301.1 NOTE: THE DESIGN LOADS
 OF THE TRUSSES WILL HAVE TO MATCH THE ROOF AND FLOOR
 LIVE AND DEAD LOADS SPECIFIED ON THE PLANS. FBC
 R802.10.1
  
 9) THE TRUSS LAYOUT FROM THE TRUSS COMPANY NEEDS TO BE
 SIGNED AND SEALED BY THE TRUSS ENGINEER AND REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. FS 471 AND CITY AMENDMENTS 107.1 NOTE: TRUSS
 DRAWINGS FOR ONE AND TWO FAMILY DWELLINGS DO NOT HAVE
 TO BE SUBMITTED FOR PLAN REVIEW. THEY CAN BE PROVIDED
 TO THE FIELD INSPECTOR AT THE ROOF FRAMING INSPECTION.
  
 10) NOTE: IN ORDER TO SPEED REVIEW TIME, PLEASE PROVIDE
 A RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS
 WERE ADDRESSED.
  