2012-04-30 14:17:2312010415
 419 33RD STREET
 NEW SFD
  
 PLEASE REDRAW THE ELECTRICAL RISER TO SHOW HOW EACH
 PANEL BOARD WILL BE FED. LOCATE THE ELECTRIC PANEL
 BOARDS ON THE PLAN. SHOW THE GROUNDING SYSTEM FOR EACH
 SUB PANEL. NEC 215.5
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 INDICATE THAT ALL GENERAL PURPOSE BRANCH CIRCUITS MUST
 BE PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008
 NEC 210.12
 THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 ADD A GFCI PROTECTED RECEPTACLE TO SERVE EACH BASIN IN
 THE SECOND FLOOR BATH. NEC 210.52 (D)
 SMOKE DETECTORS ARE REQUIRED TO BE INTERCONNECT AND
 LOCATED INSIDE AND OUTSIDE EACH SLEEPING AREA. FBC R
 313
  