Plan Review Notes
Plan Review Notes For Permit 12010415
Permit Number 12010415
Review Stop B
Sequence Number 1
Notes
Date Text
2012-05-11 15:47:342010 FBC
  
 DENIED BY BUILDING
  
 1) PLANS REFERENCE THE 2010 FBC. THE PERMIT WAS APPLIED
 FOR ON 1/19/2O12 WHICH WAS PRIOR TO THE IMPLEMENTATION
 DATE OF THE 2010 FBC AND ASCE 7- 10 ON 3/15/20102. THE
 2007 FBC W2009 REVISIONS WAS THE CODE IN EFFECT AT THE
 TIME OF APPLICATION. BECAUSE THE PLANS WERE HELD UP IN
 ZONING AND NOT SENT TO BUILDING DEPT. UNTIL AFTER THE
 CODE CHANGE IF YOU CHOOSE TO DO SO THE APPLICATION DATE
 CAN BE CHANGED TO ALLOW DESIGN UNDER THE 2010 CODE PER
 ROBERT BROWN.
  
 2) BECAUSE THE PROPOSED STRUCTURE IS LOCATED WITHIN
 1500 FEET OF THE INTER-COASTAL WATERWAY THE EXPOSURE
 CATEGORY IS C AND THE WIND SPEED FOR WEST PALM BEACH IS
 170 MPH UNDER THE 2010 CODE AND 140 UNDER THE 2007
 CODE. PLEASE REVISE.
  
 3) THE COMPONENT AND CLADDING PRESSURES SPECIFIED ON
 THE PLANS ARE TOO LOW. FBC R301.2.1 PLEASE REVISE.
  
 4) THE FRONT AND REAR ELEVATIONS ON A2.1 DO NOT HAVE
 ALL OF THE WINDOWS AND DOORS TAGGED TO CORRESPOND WITH
 THE WINDLOAD SCHEDULE. R301.2.1
  
 5) THE BOTTOM OF ALL EXTERIOR FOOTERS ARE REQUIRED BY
 FBC R403.1.4 TO BE AT LEAST 12 INCHES BELOW THE GROUND
 SURFACE. THE SOIL REPORT SUBMITTED RECOMMENDS 16" TO
 24" BELOW THE FINISHED PAD OR MONOLITHIC SLAB.
  
 6) FBC R404.1.6 REQUIRES THE FOUNDATION TO EXTEND A
 MINIMUM OF 4 INCHES ABOVE THE FINISHED GRADE ADJACENT
 TO THE FOUNDATION.
  
 7) SHOW COMPLIANCE WITH FBC R310 FOR THE REQUIRED
 EMERGENCY ESCAPE AND RESCUE OPENINGS. THE SECOND FLOOR
 BEDROOMS DO NOT COMPLY. PLEASE CLARIFY "EH" TAG SHOWN
 AT THE WINDOWS ON THE FRONT AND REAR ELEVATIONS ON
 A2.1.
  
 8) SUBMIT TWO COPIES OF A SURFACE WATER DRAINAGE PLAN
 SHOWING COMPLIANCE WITH FBC R401.3.
  
 9) SPECIFY THE BOLTS FOR THE 2 X 4 AND 2 X 6
 ATTACHMENTS TO THE CONCRETE BEAM FOR THE LOWER ROOF
 SHOWN ON WALL SECTION 3 ON A4.2. FBC R301.1
  
 10) WALL SECTION 5 ON SHEET A4.2 IS MIS-LABELED. IT IS
 A SECTION AT THE PATIO NOT THE GARAGE. CITY AMENDMENTS
 107.2.1
  
 11) SHOW COMPLIANCE WITH FBC R502.1.2 FOR DRAFTSTOPPING
 AT THE FLOOR CEILING ASSEMBLY NOT TO EXCEED 1000 SQFT.
  
 12) THERE IS NO F1 FOOTER SHOWN IN THE SCHEDULE ON
 SHEET S1.1 FOR THE C1 COLUMN PAD SHOWN ON THE
 FOUNDATION PLAN. CITY AMENDMENTS 107.2.1
  
 13) PROVIDE A DETAIL FOR THE 2 X 4 AND 2 X 6 INTERIOR
 BEARING WALLS. FBC R301.1
  
 14) SPECIFY THE CONNECTORS THAT WILL BE USED AT THE TOP
 AND BOTTOM OF THE 6 X 6 WOOD COLUMNS. FBC R301.1
  
 15) PROVIDE A DETAIL FOR THE BUILT- UP (3) 2X 6 WOOD
 COLUMN. FBC R301.1
  
 16) PROVIDE THE MISSING STRUCTURAL DETAILS FOR COLUMN
 C-5 IN THE SCHEDULE ON SHEET S1.1. FBC R301.1
  
 17) PLEASE CLARIFY THE NOTE AT THE GARAGE ON SHEET S1.1
 FOR THE 16" X 16" STRIP FOOTING. A TE 2 18" X 12"
 FOOTING IS SHOWN. CITY AMENDMENTS 107.2.1
  
 18) ON SHEET S1.2 THE TAGS FOR THE BEAMS ON THE PLAN
 ARE B-1 AND B-2 AND IN THE SCHEDULE THEY ARE BM-1 AND
 BM-2. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 19) THE NOTE ON SHEET S1.3 SPECIFIES 8D COMMON NAILS
 FOR FASTENING THE ROOF SHEATHING . FBC R803.2.3.1
 REQUIRES RING SHANK NAILS. PLEASE CORRECT.
  
 2O) THE ROOF PRESSURE AND WALL PRESSURE CHARTS ON S1.3
 ARE MISSING THE PRESSURES. FBC R301.2.1
  
 21) THERE ARE NOT ANY WOOD TO WOOD CONNECTORS SPECIFIED
 IN THE SCHEDULE ON S1.3 FOR THE 6 X 12 WOOD BEAM TO
 RAFTERS AT THE PATIO. PLEASE CORRECT. FBC R301.1
  
 22) THE PLANS APPEAR TO SHOW A NON-VENTED ATTIC WITH
 R-20 INSULATION AND THE ENERGY CALCULATIONS SPECIFY A
 R-30 VENTED ATTIC. PLEASE CORRECT. CITY AMENDMENTS
 107.2.1
  
 23) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE USED IN THE
 NON-VENTED ATTIC. FBC R316.3
  
 24) THE FORM THAT WAS SUBMITTED 1100A-08 CAN NOT BE
 USED WITH THE 2010 FBC. SEE FBC ENERGY CONSERVATION
 SECTION 405.4.
  
 25) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 26) SEVERAL OF THE PRODUCT APPROVALS HAVE BEEN
 SUPERSEDED OR EXPIRED PRIOR TO THE IMPLEMENTATION OF
 THE 2010 FBC. PLEASE REVIEW ALL TO MAKE SURE THEY ARE
 CURRENT. DCA RULE 9N-3
  
 27) THE TRUSS DRAWING THAT WERE SUBMITTED SPECIFY THE
 2007 FBC AND ASCE 7-05 WITH A 140 MPH WIND SPEED. TO
 CORRESPOND WITH PLANS DESIGNED TO THE 2010 FBC, THE
 TRUSSES WILL NEED TO DESIGNED TO THE 2010 FBC AND ASCE
 7-10 WITH A 170 MPH WIND SPEED. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 28) SPECIFY THE ROOF & FLOOR TRUSS DESIGN LIVE AND DEAD
 LOADS ON THE PLANS. FBC R301.1
  
 29) THE TRUSS DESIGN LOADS OF THE TRUSSES WILL HAVE TO
 MATCH THE ROOF AND FLOOR LIVE AND DEAD LOADS SPECIFIED
 ON THE PLANS. FBC R802.10.1
  
 30) THE TRUSS LAYOUT FROM THE TRUSS COMPANY NEEDS TO BE
 SIGNED AND SEALED BY THE TRUSS ENGINEER AND REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. FS 471 AND CITY AMENDMENTS 107.1
  
 31) NOTE: TRUSS DRAWINGS FOR ONE AND TWO FAMILY
 DWELLINGS DO NOT HAVE TO BE SUBMITTED FOR PLAN REVIEW.
 THEY CAN BE PROVIDED TO THE FIELD INSPECTOR AT THE ROOF
 FRAMING INSPECTION.
  
 32) NOTE: IN ORDER TO SPEED REVIEW TIME, PLEASE PROVIDE
 A RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS
 WERE ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW