Plan Review Notes
Plan Review Notes For Permit 12010347
Permit Number 12010347
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-02-03 12:05:19324 DATURA STREET - SUITE #209
 PERMIT #12010347
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THESE REQUIREMENTS ARE DIFFERENT THAN THE
 REQUIREMENTS OF FOR MAGNETIC LOCKS WHEREBY AN OCCUPANT
 SENSOR AND PUSH TO EXIT BUTTON ARE NEEDED IN ON THE
 EGRESS SIDE.
  
 SECTION 7.2.1.5.5 OF NFPA 101 FLORIDA EDITION 2009
 ALLOWS ELECTRICALLY CONTROLLED EGRESS DOOR ASSEMBLIES
 IF EQUIPPED WITH APPROVED LISTED HARDWARE THAT
 INCORPORATES A BUILT-IN SWITCH AND THE FOLLOWING FIVE
 CRITERIA ARE MET:
 1. THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 2. THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION THAT
 IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 3. THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 4. OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 5. LOSS OF POWER TO THE HARDWARE AUTOMATICALLY UNLOCKS
 THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  