Plan Review Notes
Plan Review Notes For Permit 12010341
Permit Number 12010341
Review Stop M
Sequence Number 1
Notes
Date Text
2012-02-02 15:48:512007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE ENERGY CALCULATIONS ARE NOT COMPLETE. IT APPEARS
 THAT THERE MAY HAVE BEEN AN ERROR WITH THE PRINTER.
 PLEASE SUBMIT TWO COMPLETE COPIES OF THE ENERGY
 CALCULATIONS AS REQUIRED BY N1100.2 OF THE 2007 FBC
 ENERGY GLITCH AMENDMENTS.
  
 2) THE HVAC SYSTEM HAS BEEN DESIGNED BY A DIFFERENT
 MECHANICAL CONTRACTOR THAN THE ONE THAT IS SIGNED ON
 THE PERMIT APPLICATION TO DO THE WORK. UNDER THE DESIGN
 AND BUILD EXEMPTION TO FLORIDA STATUTE 471.003(2)(H),
 THE MECHANICAL CONTRACTOR IS ALLOWED TO DESIGN THE
 SYSTEM ONLY IF IT IS INSTALLED BY HIM. SINCE THIS IS
 NOT THE CASE, THE MECHANICAL PLANS ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE DESIGN ENGINEER.
  
 3) ON SHEET M2 BOTH OF THE AIR HANDLERS FOR THE SECOND
 FLOOR ARE LABELED AHU #3. PLEASE CORRECT. CITY
 AMENDMENTS 106.1.1
  