Plan Review Notes For Permit 12010341 |
Permit Number |
12010341 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-23 09:11:14 | 12010341 | | 235 EDMOR RD. | | NEW CUSTOM HOME | | | | CARBON MONOXIDE DETECTORS ARE REQUIRED WITHIN 10 FEET | | OF ALL SLEEPING AREAS. FBC R313 | | ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 | | FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 | | FEET IN WIDTH HAVE A RECEPTACLE I.E. WET BAR, FRONT | | ENTRY, BEDROOM 3, UNDER STAIRCASE ETC. NEC 210.52 | | PANEL BOARD FEEDERS APPEAR TO BE UNDERSIZED. MIN. 3/0 | | REQUIRED FOR 200 AMPERE BREAKER. NEC T. 310.16 | | PANEL ?C? EQUIPMENT GROUND SHOULD BE #6. NEC T. 250.122 | | INDICATE LOCATION OF ALL PANEL BOARDS AND THE | | ELECTRICAL SERVICE. NEC 215.5 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|