2012-01-23 09:11:1412010341
 235 EDMOR RD.
 NEW CUSTOM HOME
  
 CARBON MONOXIDE DETECTORS ARE REQUIRED WITHIN 10 FEET
 OF ALL SLEEPING AREAS. FBC R313
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE I.E. WET BAR, FRONT
 ENTRY, BEDROOM 3, UNDER STAIRCASE ETC. NEC 210.52
 PANEL BOARD FEEDERS APPEAR TO BE UNDERSIZED. MIN. 3/0
 REQUIRED FOR 200 AMPERE BREAKER. NEC T. 310.16
 PANEL ?C? EQUIPMENT GROUND SHOULD BE #6. NEC T. 250.122
 INDICATE LOCATION OF ALL PANEL BOARDS AND THE
 ELECTRICAL SERVICE. NEC 215.5
  