Plan Review Notes For Permit 12010253 |
Permit Number |
12010253 |
|
Review Stop |
ENG |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-30 10:03:11 | ADDITIONAL INFORMATION SUBMITTED CLARIFYING WATER | | SERVICE AND SEWER CONNECTION. | | SEE CITY STANDARD DETAILS SUPPLIED. | | | | | | MANUEL GONZALEZ | | CITY OF WPB | | (561) 644-7301 | | [email protected] | 2012-01-22 11:32:19 | INFORMATION SHOWN IS AS FOLLOWS: | | | | #1 SEWER APPEARS TO BE COMING FROM ADJACENT SITE. | | (ORDINANCE 2593-92 DOES NOT ALLOW SITE TO BE SERVED | | THRU SOMEONE ELSE'S PROPERTY) | | | | #2 SHOW FULL EXTENT OF WATER AND SEWER SERVICE TO | | CITY'S POINT OF CONNECTION. | | | | #3 WATER SERVICE MUST SHOW A BACKFLOW (RPPA) JUST | | INSIDE YOUR PROPERTY LINE AFTER THE CITY'S WATER METER. | | | | #4 NOTE POTABLE WATER METER SIZE. | | | | YOU MAY CONTACT ME DIRECTLY SO THAT WE CAN DICUSS | | TEMPORARY SERVICES AND FEES THAT WILL APPLY THRU | | CITY'S PUBLIC UTILITIES DEPARTMENT - CUSTOMER SERVICE. | | | | MANUEL JULIAN GONZALEZ | | ENGINEERING PROJECT COORDINATOR | | ENGINEERING SERVICES DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | | | DIRECT: (561) 494-1085 | | | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|