Plan Review Notes For Permit 12010221 |
Permit Number |
12010221 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-19 14:21:11 | 12010221 | | 5200 N. FLAGLER DR. #2102 | | INTERIOR CONDO RENOVATION | | | | SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED. | | PLEASE PROVIDE THE FOLLOWING: | | INDICATE THE SIZE OF THE NEW ELECTRICAL PANEL. PROVIDE | | A PANEL SCHEDULE. SHOW THE FEEDER SIZE AND EXISTING | | OVER CURRENT PROTECTION. ON THE FLOOR PLAN SHOW THE | | LOCATION OF ALL NEW AND EXISTING LIGHTING OUTLETS, | | RECEPTACLE OUTLETS AND SMOKE DETECTORS. NEC 215.5 | | VERIFY THE KITCHEN COUNTER TOP RECEPTACLES AND BATHROOM | | RECEPTACLES ARE GFCI PROTECTED. NEC 210.8 | | INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER | | RESISTANT. NEC 406.11 | | ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE | | PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC | | 210.12 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|