Plan Review Notes For Permit 12010219 |
Permit Number |
12010219 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-12 11:44:52 | 505 CLEMATIS STREET | | PERMIT #12010219 | | MASTER #11090836 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVIDE SPRINKLER COVERAGE (X2) IN THE EXISTING CEILING | | OF THE ENTRY DOOR AS THE EXISTING UPRIGHT SPRINKLERS DO | | NOT APPEAR TO PROTECT THIS AREA DUE TO THE POSSIBLE | | SPRAY OBSTRUCTION CREATED BY THE EXISTING BEAM. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | |
|