Plan Review Notes For Permit 12010196
Permit Number 12010196
Review Stop B
Sequence Number 3
Notes
Date Text
2012-12-11 12:21:51BUILDING PLAN REVIEW
 PERMIT: 12010196
 ADD: 1860 N TAMARIND AVE.
 CONT: HARTNETT BUILDING GROUP
 TEL: (561)523-5902
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
  
 PROVISO: 11/09/2012 ARCHITECT IS LOOK AT OPTIONS FOR
 SAFETY GLAZING.
 SHEET A2.1 WINDOW SCHEDULE NOTE # 3 INDICATES ALL
 SAFETY GLAZING IN HAZARDOUS AREAS SHALL BE TEMPERED.
 THE WINDOW SCHEDULE DOES INDICATE
 WINDOW TYPE E BUT NOT TYPE A WHERE THE WINDOW WILL BE
 NEXT TO THE STAIR IS THE DESIGNER USING THE LARGE
 MISSILE TESTED LAMINATED GLAZING AS MEETING THE SAFETY
 GLAZING REQUIREMENTS UNDER 2406.4.
  
 ROOFING : FL GAF-ELK ASPHALT ROOF SHINGLES
 FL 10124-R3
 EVAL RE: 01506.01.08-R4
  
 JAMES A. WITMER CBO