Plan Review Notes
Plan Review Notes For Permit 12010196
Permit Number 12010196
Review Stop B
Sequence Number 2
Notes
Date Text
2012-10-31 10:54:21BUILDING PLAN REVIEW
 PERMIT: 12010196
 ADD: 1860 N TAMARIND AVE.
 CONT: HARTNETT BUILDING GROUP
 TEL: (561)523-5902
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 OCT. 31/ 2012
 ACTION: DENIED
  
 1) 11/09/2012 COMPLIED, AARCHITECT RED LINED PLANS.
 SHEET A1.1 SEMI- COMPLIED. THE PLANS ARE MISSING THE
 ACCESS AISLE AS REQUIRED BY ANSI 4.6. SITE PLAN DOES
 NOT COMPLIANCE WITH THE FAIR HOUSING ACT, AND ANSI
 A117.1 4.3 ACCESSIBLE ROUTE, AN ACCESSIBLE ROUTE TO ALL
 SITE AMENITIES (DUMPSTER), PARKING SPACES, ACCESS
 AISLES, CURB RAMPS, RAMPS SLOPES, CROSS SLOPES &
 ACCESIBILTY TO PUBLIC TRANS PORTATION.
 \
  
 12) COMPLIED. 11/14/2012 CLARIFICATION LETTER FROM
 ONMJ.
 2ND REQUEST. SHEET S1 VERSES SHEET A2.1 DOOR # 2 IS
 INDICATED AS A 6'-0" WIDE DOOR OPENING, WHERE AS S1
 INDICATES TTHE BLOCK OPENING TO BE NARROWER. PLEASE
 ALSO REVIEW THE BEAM SCHEDULE ON S3, VERSES S1 AND S2
 ALL BEAMS ARE LABELED BB-1 WITH NO STIRRUPS OR HOOPS
 (HAIRPINS DETAIL 4 / SHEET S4) ) OVER THE WINDOWS AND
 DOORS. ACI 530 # 7.5.3.1 SHEAR REINFORCEMENT SHALL BE
 PROVIDED PARALLEL TO THE DIRECTION OF APPLIED FORCE.
 SPACING OF SHEAR REINFORCEMENT SHALL NOT EXCEED THE
 LESSEER OF D/2 OR 48 INCHES.
  
 13-15) COMPLIED.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NEW COMMENTS
  
 17) 11/09/2012 COMPLIED, AARCHITECT RED LINED PLANS.
 SHEET A2.1 PLEASE REVIEW EGRESS WINDOW NOTE IN REGARDS
 TO TOTAL GLAZED AREA VERSES THE REQUIRED CLEAR OPENING
 REQUIREMENTS FOR FIRST FLOOR VERSES SECOND FLOOR. 2007
 FBC-B SECTION 1026.2.
  
 18) PROVISO: 11/09/2012 ARCHITECT IS LOOK AT OPTIONS
 FOR SAFETY GLAZING.
 SHEET A2.1 WINDOW SCHEDULE NOTE # 3 INDICATES ALL
 SAFETY GLAZING IN HAZARDOUS AREAS SHALL BE TEMPERED.
 THE WINDOW SCHEDULE DOES INDICATE
 WINDOW TYPE E BUT NOT TYPE A WHERE THE WINDOW WILL BE
 NEXT TO THE STAIR IS THE DESIGNER USING THE LARGE
 MISSILE TESTED LAMINATED GLAZING AS MEETING THE SAFETY
 GLAZING REQUIREMENTS UNDER 2406.4.
  
 19) 11/14/2012 LETTER FROM ARCHITECT DAVID LAWRENCE TO
 DOUG WISE B.O. ASKING FOR REVIEW OF ALTERNATE MATERIALS
 & METHODS, SUBMITTED TO ROBERT BROWNS OFFICE. JW.
  
 11/09/2012 ARCHITECT IS TO WRITE LETTER FOR ALTERNATE
 MATERIALS AND METHODS 2010 FBC ADMINISTRATIVE CODE
 104.11.THE COVERSHEET A1.0 UNDER THE BUILDING DESIGN
 LIST THIS BUILDING AS A TYPE V-B UNSPRINKLERED. BOTH
 THE BUILDING AND FIRE CODES REQUIRE ALL R TYPE
 OCCUPANCIES TO BE FIRE SPRINKLERED WIT THE EXCEPTION OF
 ONE AND TWO FAMILY DWELLINGS THAT ARE REVIEWED UNDER
 THE 2007 FBC-R RESIDENTIAL CODE.
 2007-09 FBC-B 903.2.7 REQUIRES FIRE SPRINKLERS. WE DO
 UNDERSTAND THERE WAS TALK WITH THE FIRE DEPARTMENT
 ABOUT FIRE SPRINKLER REQUIREMENTS BUT NO OTHER
 INFORMATION HAS BEEN PROVIDED BY THE FIRE DEPARTMENT AS
 TO THE RESULTS OF SUCH MEETING. CHIEF DANIELS HAS
 ENTERED IN THE PLAN REVIEW FIELD RESULTS THAT A MEETING
 WITH THE DESIGNER HAD OCCURED WHICH HAS KEPT THE PERMIT
 ALIVE SINCE THE LAST LISTED ACTIVITY. THE DESIGNER OF
 RECORD ON THE COMMENT RESPONCE SHEET INDICATES THEY ARE
 GOING WITH A PERFORMANCE BASED METHOD IN LEIU OF FIRE
 SPRINKLERS. THE COVER SHEET DOES NOT INDICATE A
 PREFORMANCE BASED METHOD VERSES FIRE SPINKLERS. IF THE
 DESIGNER OF RECORD IS PROPOSING TO USE ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION (104.11
 WEST PALM BEACH ADMINISTRATIVE CODE) A LETTER TO THE
 BUILDING OFFICIAL REQUESTING THE USE OF ALTERNANTE
 MATERIAL AND METHODS TO BE SUBSTITUTED. WHEN ALTERNANTE
 LIFE SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING
 GUIDE OF PERFORMANCE- BASED FIRE PROTECTION ANALYSIS
 AND DESIGN OF BUILDINGS OR OTHER METHODS APPROVED BY
 THE BUILDING OFFICIAL MAY BE USED.
  
 NOTE NO PRODUCT APPROVALS HAVE BEEN SUBMITTED FOR
 ROOFING AT THIS TIME, A SEPERATE PERMIT, REVIEW AND
 ASSOCIATED FEES SHALL OCCUR.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  