2012-10-31 10:54:21 | BUILDING PLAN REVIEW |
| PERMIT: 12010196 |
| ADD: 1860 N TAMARIND AVE. |
| CONT: HARTNETT BUILDING GROUP |
| TEL: (561)523-5902 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2ND REVIEW |
| OCT. 31/ 2012 |
| ACTION: DENIED |
| |
| 1) 11/09/2012 COMPLIED, AARCHITECT RED LINED PLANS. |
| SHEET A1.1 SEMI- COMPLIED. THE PLANS ARE MISSING THE |
| ACCESS AISLE AS REQUIRED BY ANSI 4.6. SITE PLAN DOES |
| NOT COMPLIANCE WITH THE FAIR HOUSING ACT, AND ANSI |
| A117.1 4.3 ACCESSIBLE ROUTE, AN ACCESSIBLE ROUTE TO ALL |
| SITE AMENITIES (DUMPSTER), PARKING SPACES, ACCESS |
| AISLES, CURB RAMPS, RAMPS SLOPES, CROSS SLOPES & |
| ACCESIBILTY TO PUBLIC TRANS PORTATION. |
| \ |
| |
| 12) COMPLIED. 11/14/2012 CLARIFICATION LETTER FROM |
| ONMJ. |
| 2ND REQUEST. SHEET S1 VERSES SHEET A2.1 DOOR # 2 IS |
| INDICATED AS A 6'-0" WIDE DOOR OPENING, WHERE AS S1 |
| INDICATES TTHE BLOCK OPENING TO BE NARROWER. PLEASE |
| ALSO REVIEW THE BEAM SCHEDULE ON S3, VERSES S1 AND S2 |
| ALL BEAMS ARE LABELED BB-1 WITH NO STIRRUPS OR HOOPS |
| (HAIRPINS DETAIL 4 / SHEET S4) ) OVER THE WINDOWS AND |
| DOORS. ACI 530 # 7.5.3.1 SHEAR REINFORCEMENT SHALL BE |
| PROVIDED PARALLEL TO THE DIRECTION OF APPLIED FORCE. |
| SPACING OF SHEAR REINFORCEMENT SHALL NOT EXCEED THE |
| LESSEER OF D/2 OR 48 INCHES. |
| |
| 13-15) COMPLIED. |
| |
| 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| NEW COMMENTS |
| |
| 17) 11/09/2012 COMPLIED, AARCHITECT RED LINED PLANS. |
| SHEET A2.1 PLEASE REVIEW EGRESS WINDOW NOTE IN REGARDS |
| TO TOTAL GLAZED AREA VERSES THE REQUIRED CLEAR OPENING |
| REQUIREMENTS FOR FIRST FLOOR VERSES SECOND FLOOR. 2007 |
| FBC-B SECTION 1026.2. |
| |
| 18) PROVISO: 11/09/2012 ARCHITECT IS LOOK AT OPTIONS |
| FOR SAFETY GLAZING. |
| SHEET A2.1 WINDOW SCHEDULE NOTE # 3 INDICATES ALL |
| SAFETY GLAZING IN HAZARDOUS AREAS SHALL BE TEMPERED. |
| THE WINDOW SCHEDULE DOES INDICATE |
| WINDOW TYPE E BUT NOT TYPE A WHERE THE WINDOW WILL BE |
| NEXT TO THE STAIR IS THE DESIGNER USING THE LARGE |
| MISSILE TESTED LAMINATED GLAZING AS MEETING THE SAFETY |
| GLAZING REQUIREMENTS UNDER 2406.4. |
| |
| 19) 11/14/2012 LETTER FROM ARCHITECT DAVID LAWRENCE TO |
| DOUG WISE B.O. ASKING FOR REVIEW OF ALTERNATE MATERIALS |
| & METHODS, SUBMITTED TO ROBERT BROWNS OFFICE. JW. |
| |
| 11/09/2012 ARCHITECT IS TO WRITE LETTER FOR ALTERNATE |
| MATERIALS AND METHODS 2010 FBC ADMINISTRATIVE CODE |
| 104.11.THE COVERSHEET A1.0 UNDER THE BUILDING DESIGN |
| LIST THIS BUILDING AS A TYPE V-B UNSPRINKLERED. BOTH |
| THE BUILDING AND FIRE CODES REQUIRE ALL R TYPE |
| OCCUPANCIES TO BE FIRE SPRINKLERED WIT THE EXCEPTION OF |
| ONE AND TWO FAMILY DWELLINGS THAT ARE REVIEWED UNDER |
| THE 2007 FBC-R RESIDENTIAL CODE. |
| 2007-09 FBC-B 903.2.7 REQUIRES FIRE SPRINKLERS. WE DO |
| UNDERSTAND THERE WAS TALK WITH THE FIRE DEPARTMENT |
| ABOUT FIRE SPRINKLER REQUIREMENTS BUT NO OTHER |
| INFORMATION HAS BEEN PROVIDED BY THE FIRE DEPARTMENT AS |
| TO THE RESULTS OF SUCH MEETING. CHIEF DANIELS HAS |
| ENTERED IN THE PLAN REVIEW FIELD RESULTS THAT A MEETING |
| WITH THE DESIGNER HAD OCCURED WHICH HAS KEPT THE PERMIT |
| ALIVE SINCE THE LAST LISTED ACTIVITY. THE DESIGNER OF |
| RECORD ON THE COMMENT RESPONCE SHEET INDICATES THEY ARE |
| GOING WITH A PERFORMANCE BASED METHOD IN LEIU OF FIRE |
| SPRINKLERS. THE COVER SHEET DOES NOT INDICATE A |
| PREFORMANCE BASED METHOD VERSES FIRE SPINKLERS. IF THE |
| DESIGNER OF RECORD IS PROPOSING TO USE ALTERNATE |
| MATERIALS, DESIGN AND METHODS OF CONSTRUCTION (104.11 |
| WEST PALM BEACH ADMINISTRATIVE CODE) A LETTER TO THE |
| BUILDING OFFICIAL REQUESTING THE USE OF ALTERNANTE |
| MATERIAL AND METHODS TO BE SUBSTITUTED. WHEN ALTERNANTE |
| LIFE SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING |
| GUIDE OF PERFORMANCE- BASED FIRE PROTECTION ANALYSIS |
| AND DESIGN OF BUILDINGS OR OTHER METHODS APPROVED BY |
| THE BUILDING OFFICIAL MAY BE USED. |
| |
| NOTE NO PRODUCT APPROVALS HAVE BEEN SUBMITTED FOR |
| ROOFING AT THIS TIME, A SEPERATE PERMIT, REVIEW AND |
| ASSOCIATED FEES SHALL OCCUR. |
| |
| |