2012-02-09 12:00:0012010196
 1860 N. TAMARIND AVE.
 MULTIFAMILY DWELLING
  
 ADD RECEPTACLES: UNIT ?B? SECOND FLOOR AT TWO FOOT WALL
 SPACE AT CLOSET IN BEDROOM 2, UNIT ?C? SECOND FLOOR
 BALCONY INCLUDING GFCI PROTECTION, UNIT ?D? ON WALL
 SPACE NEXT TO AHU. NEC 210.52
  
 ADD A SMALL APPLIANCE CIRCUIT TO THE PANEL SCHEDULE FOR
 UNITS ?A? AND ?D?. NEC 210.52 (C)
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 SERVICE FEEDER OVER CURRENT PROTECTION FOR PARALLEL 400
 MCM FEEDERS IS LIMITED TO 700 AMPERES. NEC T. 310.16,
 240 .6
  
 ROBERT LECKY
 ELECTRIC PLAN REVIEWER
 [email protected]
 561-805-6718
  