Plan Review Notes For Permit 12010196 |
Permit Number |
12010196 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-02-09 12:00:00 | 12010196 | | 1860 N. TAMARIND AVE. | | MULTIFAMILY DWELLING | | | | ADD RECEPTACLES: UNIT ?B? SECOND FLOOR AT TWO FOOT WALL | | SPACE AT CLOSET IN BEDROOM 2, UNIT ?C? SECOND FLOOR | | BALCONY INCLUDING GFCI PROTECTION, UNIT ?D? ON WALL | | SPACE NEXT TO AHU. NEC 210.52 | | | | ADD A SMALL APPLIANCE CIRCUIT TO THE PANEL SCHEDULE FOR | | UNITS ?A? AND ?D?. NEC 210.52 (C) | | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | SERVICE GROUND. NEC 250.94 | | | | SERVICE FEEDER OVER CURRENT PROTECTION FOR PARALLEL 400 | | MCM FEEDERS IS LIMITED TO 700 AMPERES. NEC T. 310.16, | | 240 .6 | | | | ROBERT LECKY | | ELECTRIC PLAN REVIEWER | | [email protected] | | 561-805-6718 | | |
|