2012-01-20 11:02:35 | BUILDING PLAN REVIEW |
| PERMIT: 12010196 |
| ADD: 1860 N TAMARIND AVE. |
| CONT: HARTNETT BUILDING GROUP |
| TEL: (561)523-5902 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET A1.1 SITE PLAN DOES NOT COMPLIANCE WITH THE |
| FAIR HOUSING ACT, AND ANSI A117.1 4.3 ACCESSIBLE ROUTE, |
| AN ACCESSIBLE ROUTE TO ALL SITE AMENITIES (DUMPSTER), |
| PARKING SPACES, ACCESS AISLES, CURB RAMPS, RAMPS |
| SLOPES, CROSS SLOPES & ACCESIBILTY TO PUBLIC TRANS |
| PORTATION. |
| |
| 2) SHEET A3.1 UNIT A AND (REVERSE A) BOTH INDICATE A |
| BI-FOLD DOOR # 3 WITH A WIDTH OF 2'-6" PLEASE SEE ANSI |
| 4.13 FOR INTERIOR USABLE DOORS TO HAVE A CLEAR WIDTH OF |
| 32 INCHES. |
| |
| 3) SHEET A3.1 UNIT A AND REVERSE A PLEASE DIMENSION |
| FROM THE SINK CENTERLINE TO THE INSIDE CORNER AS WELL |
| AS FROM THE INSIDE CORNER TO THE CENTER LINE OF THE |
| STOVE. PLEASE PROVIDE THE CLEAR FLOOR SPACE (30X48) |
| CENTER-LINED ON THE APPLIANCES IT APPEARS THERE MAY NOT |
| BE ENOUGH ROOM TO ACCOMADATE THE CLEAR FLOOR SPACE FOR |
| A SIDE APPROACH. |
| |
| 4) SHEET A3.1 UNIT D INDICATES A BI-FOLD DOOR # 2 WITH |
| A WIDTH OF 2'-6" PLEASE SEE ANSI 4.13 FOR INTERIOR |
| USABLE DOORS TO HAVE A CLEAR WIDTH OF 32 INCHES. |
| |
| 5) SHEET A3.1 UNIT D PLEASE DIMENSION FROM THE SINK |
| CENTERLINE TO THE INSIDE CORNER AS WELL AS FROM THE |
| INSIDE CORNER TO THE CENTER LINE OF THE STOVE. PLEASE |
| PROVIDE THE CLEAR FLOOR SPACE (30X48) CENTER-LINED ON |
| THE APPLIANCES IT APPEARS THERE MAY NOT BE ENOUGH ROOM |
| TO ACCOMADATE THE CLEAR FLOOR SPACE FOR A SIDE |
| APPROACH. |
| |
| 6) SHEET A3.1 FOR BOTH A & D BATHROOM UNITS PLEASE |
| DIMENSION LAVATORY AND WATER CLOSET LOCATIONS FROM WALL |
| TO CENTER LINE OF FIXTURE AND OR FROM CENTERLINE OF |
| FIXTURE TO CENTERLINE OF FIXTURE. PLEASE PROVIDE WHICH |
| TYPE OF RESTROOM TYPE A OR B HAS BEEN PROVIDED. |
| |
| 7) SHEET A3.2 FOR B UNIT & A3.3 FOR C UNIT BOTH ARE |
| MISSING ATTIC ACCESS FBC-B 11209.2. |
| |
| 8) SHEET A5.2 THE SINGLE STORY CUT SECTION OF WALL DOES |
| INDICATE THE USE OF FIRE BLOCKING AT THE CEILING LINE |
| BUT THE 2 STORY DETAILS DO NOT INDICATE THE USE OF FIRE |
| BLOCKING AT THE CEILING. |
| |
| 9) SHEET A5.2 FIRE BLOCKING NOTE # 2 INDICATES THE USE |
| OF FIBERGLASS BATTS AND BLANKETS AS AN ALTERNATIVE |
| FIREBLOCKING MATERIAL. PLEASE PROVIDE THE MANUFACTURERS |
| SPEC FOR THIS TYPE INSULATION TO BE USED AS A FIRE |
| BLOCKING MATERIAL. 106.1.2 ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 10) SHEET A6.1 INDICATES THE USE OF WOOD SUB-BUCKS AT |
| WINDOWS AND DOOR. THE DETAILS INDICATE THAT THE BUCKS |
| ARE NOT AS WIDE AS THE DOOR OR WINDOW FRAME. PLEASE |
| REVIEW FBC-B 1714.5.4.2. MASONRY, CONCRETE OR OTHER |
| STRUCTURAL SUBSTRATE. |
| |
| 11) PLEASE REVIEW SHEET S-1 VERSES A3.1, SHEET S-1 FOR |
| UNITS D, UNIT A AND REVERSE A THEY ALL SHOW A DROPPED |
| MONOLITHIS SLAB AT THE FRONT ENTRY PORCH VERSES A3.1 |
| WHICH INDICATES THE ENTRY PORCH FLOOR LEVEL WITH THE |
| INTERIOR SLAB SINCE THESE UNITS ARE FAIR HOUSING |
| NEEDING AN ACCESSIBLE ENTRY. |
| |
| 12) SHEET S1 VERSES SHEET A2.1 DOOR # 2 IS INDICATED AS |
| A 6'-0" WIDE DOOR OPENING, WHERE AS S1 INDICATES TTHE |
| BLOCK OPENING TO BE NARROWER. PLEASE ALSO REVIEW THE |
| BEAM SCHEDULE ON S3, VERSES S1 AND S2 ALL BEAMS ARE |
| LABELED BB-1 WITH NO STIRRUPS OR HOOPS OVER THE WINDOWS |
| AND DOORS. ACI 530 # 7.5.3.1 SHEAR REINFORCEMENT SHALL |
| BE PROVIDED PARALLEL TO THE DIRECTION OF APPLIED FORCE. |
| SPACING OF SHEAR REINFORCEMENT SHALL NOT EXCEED THE |
| LESSEER OF D/2 OR 48 INCHES. |
| |
| 13) SHEET A2.1 UNIT B UPSTAIRS RESTROOM WINDOW TYPE B, |
| THE SILL HEIGHT IS UNKNOWN MAY OR MAY NOT BE CLASSIFIED |
| AS A HAZARDOUS LOCATION FBC-B 2406.3. |
| |
| 14) SHEET A2.1 UNIT B UPSTAIRS FRONT WINDOW TYPE "B" |
| WILL NEED PRODUCT APPROVAL FOR MULLIONS. THE PGT SH-800 |
| ALUMINUM SINGLE HUNG REPORT 07-0801.03 DOES NOT |
| INDICATE THE USE OF MULLIONS WITHIN THE REPORT. FBC-B |
| 1609 COMPONENTS AND CLADDING & RULE 9N-3(31)(B). |
| |
| 15) SHEET A2.1 NOTE FOR HOLLOW METAL EXTERIOR DOOR NOA |
| # 10-0209.07 NO APPROVALS WERE SUBMITTED. |
| |
| 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |