2012-01-20 11:02:35BUILDING PLAN REVIEW
 PERMIT: 12010196
 ADD: 1860 N TAMARIND AVE.
 CONT: HARTNETT BUILDING GROUP
 TEL: (561)523-5902
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A1.1 SITE PLAN DOES NOT COMPLIANCE WITH THE
 FAIR HOUSING ACT, AND ANSI A117.1 4.3 ACCESSIBLE ROUTE,
 AN ACCESSIBLE ROUTE TO ALL SITE AMENITIES (DUMPSTER),
 PARKING SPACES, ACCESS AISLES, CURB RAMPS, RAMPS
 SLOPES, CROSS SLOPES & ACCESIBILTY TO PUBLIC TRANS
 PORTATION.
  
 2) SHEET A3.1 UNIT A AND (REVERSE A) BOTH INDICATE A
 BI-FOLD DOOR # 3 WITH A WIDTH OF 2'-6" PLEASE SEE ANSI
 4.13 FOR INTERIOR USABLE DOORS TO HAVE A CLEAR WIDTH OF
 32 INCHES.
  
 3) SHEET A3.1 UNIT A AND REVERSE A PLEASE DIMENSION
 FROM THE SINK CENTERLINE TO THE INSIDE CORNER AS WELL
 AS FROM THE INSIDE CORNER TO THE CENTER LINE OF THE
 STOVE. PLEASE PROVIDE THE CLEAR FLOOR SPACE (30X48)
 CENTER-LINED ON THE APPLIANCES IT APPEARS THERE MAY NOT
 BE ENOUGH ROOM TO ACCOMADATE THE CLEAR FLOOR SPACE FOR
 A SIDE APPROACH.
  
 4) SHEET A3.1 UNIT D INDICATES A BI-FOLD DOOR # 2 WITH
 A WIDTH OF 2'-6" PLEASE SEE ANSI 4.13 FOR INTERIOR
 USABLE DOORS TO HAVE A CLEAR WIDTH OF 32 INCHES.
  
 5) SHEET A3.1 UNIT D PLEASE DIMENSION FROM THE SINK
 CENTERLINE TO THE INSIDE CORNER AS WELL AS FROM THE
 INSIDE CORNER TO THE CENTER LINE OF THE STOVE. PLEASE
 PROVIDE THE CLEAR FLOOR SPACE (30X48) CENTER-LINED ON
 THE APPLIANCES IT APPEARS THERE MAY NOT BE ENOUGH ROOM
 TO ACCOMADATE THE CLEAR FLOOR SPACE FOR A SIDE
 APPROACH.
  
 6) SHEET A3.1 FOR BOTH A & D BATHROOM UNITS PLEASE
 DIMENSION LAVATORY AND WATER CLOSET LOCATIONS FROM WALL
 TO CENTER LINE OF FIXTURE AND OR FROM CENTERLINE OF
 FIXTURE TO CENTERLINE OF FIXTURE. PLEASE PROVIDE WHICH
 TYPE OF RESTROOM TYPE A OR B HAS BEEN PROVIDED.
  
 7) SHEET A3.2 FOR B UNIT & A3.3 FOR C UNIT BOTH ARE
 MISSING ATTIC ACCESS FBC-B 11209.2.
  
 8) SHEET A5.2 THE SINGLE STORY CUT SECTION OF WALL DOES
 INDICATE THE USE OF FIRE BLOCKING AT THE CEILING LINE
 BUT THE 2 STORY DETAILS DO NOT INDICATE THE USE OF FIRE
 BLOCKING AT THE CEILING.
  
 9) SHEET A5.2 FIRE BLOCKING NOTE # 2 INDICATES THE USE
 OF FIBERGLASS BATTS AND BLANKETS AS AN ALTERNATIVE
 FIREBLOCKING MATERIAL. PLEASE PROVIDE THE MANUFACTURERS
 SPEC FOR THIS TYPE INSULATION TO BE USED AS A FIRE
 BLOCKING MATERIAL. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 10) SHEET A6.1 INDICATES THE USE OF WOOD SUB-BUCKS AT
 WINDOWS AND DOOR. THE DETAILS INDICATE THAT THE BUCKS
 ARE NOT AS WIDE AS THE DOOR OR WINDOW FRAME. PLEASE
 REVIEW FBC-B 1714.5.4.2. MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE.
  
 11) PLEASE REVIEW SHEET S-1 VERSES A3.1, SHEET S-1 FOR
 UNITS D, UNIT A AND REVERSE A THEY ALL SHOW A DROPPED
 MONOLITHIS SLAB AT THE FRONT ENTRY PORCH VERSES A3.1
 WHICH INDICATES THE ENTRY PORCH FLOOR LEVEL WITH THE
 INTERIOR SLAB SINCE THESE UNITS ARE FAIR HOUSING
 NEEDING AN ACCESSIBLE ENTRY.
  
 12) SHEET S1 VERSES SHEET A2.1 DOOR # 2 IS INDICATED AS
 A 6'-0" WIDE DOOR OPENING, WHERE AS S1 INDICATES TTHE
 BLOCK OPENING TO BE NARROWER. PLEASE ALSO REVIEW THE
 BEAM SCHEDULE ON S3, VERSES S1 AND S2 ALL BEAMS ARE
 LABELED BB-1 WITH NO STIRRUPS OR HOOPS OVER THE WINDOWS
 AND DOORS. ACI 530 # 7.5.3.1 SHEAR REINFORCEMENT SHALL
 BE PROVIDED PARALLEL TO THE DIRECTION OF APPLIED FORCE.
 SPACING OF SHEAR REINFORCEMENT SHALL NOT EXCEED THE
 LESSEER OF D/2 OR 48 INCHES.
  
 13) SHEET A2.1 UNIT B UPSTAIRS RESTROOM WINDOW TYPE B,
 THE SILL HEIGHT IS UNKNOWN MAY OR MAY NOT BE CLASSIFIED
 AS A HAZARDOUS LOCATION FBC-B 2406.3.
  
 14) SHEET A2.1 UNIT B UPSTAIRS FRONT WINDOW TYPE "B"
 WILL NEED PRODUCT APPROVAL FOR MULLIONS. THE PGT SH-800
 ALUMINUM SINGLE HUNG REPORT 07-0801.03 DOES NOT
 INDICATE THE USE OF MULLIONS WITHIN THE REPORT. FBC-B
 1609 COMPONENTS AND CLADDING & RULE 9N-3(31)(B).
  
 15) SHEET A2.1 NOTE FOR HOLLOW METAL EXTERIOR DOOR NOA
 # 10-0209.07 NO APPROVALS WERE SUBMITTED.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  