Plan Review Notes For Permit 12010189 |
Permit Number |
12010189 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-18 11:04:50 | PLEASE SUBMIT AN ELECTRICAL DETAIL FOR THE ILLUMINATION | | OF THE NEW SIGN. EACH SIGN FEEDER CIRCUIT SHALL BE | | CONTROLLED BY ONE OR MORE SWITCHES THAT ARE WITHIN SITE | | OF THE CONTROLLER AND ALSO WITH IN SIGHT OF THE SIGN. | | NEC 600.6 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|